Ductwork Sizing Chart Single Blower

Ductwork Sizing Chart Dual Blowers

Blower Size

Duct Size

(Inches)

Duct Length

(Inches)

Blower Size

Duct Size

(Inches)

Duct Length

(Inches)

10

14 x 14

30

222

77 x 28

66

12

16 x 16

36

225

88 x 32

75

15

20 x 20

45

227

96 x 36

81

18

24 x 24

54

230

104 x 38

90

20

26 x 26

60

233

116 x 44

99

22

30 x 30

66

236

122 x 44

108

25

32 x 32

75

27

36 x 36

81


WARNING!!

Failure to undersize ductwork size or length

may cause system affect and reduce the

performance of the equipment.

Using the unit to support the ductwork may

cause damage to the units casing.

30

38 x 38

90

33

44 x 44

99

36

44 x 44

108

Installation Examples

Figure 1: Horizontal Roof Top Installation

Down discharge AMU reduces ductwork

Hood weight supported by support legs

Union, regulator, and shut-off

Roof curb supports unit

Intake facing away from prevailing winds

Figure 2: Vertical Outdoor Ground Installation

Side discharge AMU reduces ductwork

Support stand on concrete pad

Union, regulator, and shut-off

Filter section inside support stand

Ease of serviceability on ground