FloAire FAV-M User Manual

Page 20

Advertising
background image

20

Close the burner gas shut off valve

This will allow the unit to fire the pilot only and will be opened at a later time

Set the Burner Intake On Off Switch is set above the outside air temperature

Turn the burner service switch ON

The Fireye Flame Safety Control energizes the ignition transformer and pilot gas valve
After the pilot flame is established, the main gas valves will open

At this time the pilot will be the only flame in the burner

The pilot regulator should be adjusted so the pilot flame signal is above 15 VDC

Use the DC terminals under the Fireye cover to read the pilot flame signal
This will ensure that the unit will start in cold damp weather with a strong pilot flame signal

Record the pilot flame signal in the Start-Up Sheet
Record the low and high fire flame signal on the Start-Up Sheet

CLOSE VALVE

SET DIAL 10

DEGREES ABOVE

OUTDOOR TEMP

BURNER SERVICE
SWITCH

PILOT REGULATOR

POSITIVE TERMINAL

NEGATIVE TERMINAL

+

-