Close the burner gas shut off valve
This will allow the unit to fire the pilot only and will be opened at a later time
Set the Burner Intake On Off Switch is set above the outside air temperature
Turn the burner service switch ON
The Fireye Flame Safety Control energizes the ignition transformer and pilot gas valve
After the pilot flame is established, the main gas valves will open
At this time the pilot will be the only flame in the burner
The pilot regulator should be adjusted so the pilot flame signal is above 15 VDC
Use the DC terminals under the Fireye cover to read the pilot flame signal
This will ensure that the unit will start in cold damp weather with a strong pilot flame signal
Record the pilot flame signal in the Start-Up Sheet
Record the low and high fire flame signal on the Start-Up Sheet