Setting High Fire – Discharge Temp Method

Open the Burner Gas Shut Off Valve

Measure the intake air temperature.
Add the intake air temperature to the units nameplate design temperature rise.
This result will be the desired high fire discharge temperature.

Example: Intake Temp 70 F
Design Temp Rise

72 F

Discharge Temp

142 F

Use the Maxitrol Amplifier to override the heater

into high fire.

On the A1014 amplifier remove the #4 wire
On the A1044 amplifier remove the #2 and #4

wire

On the M-Series adjust the set-point to be

160 F

Adjust the manifold gas pressure to achieve the

desired discharge air temperature.

See the details for the high fire pressure

adjustment locations.

On manifolds with an MR212 modulation

valve, adjust the small regulator inside the
MR212 modulation valve

On manifolds with either an M511 or M611

modulation valve, adjust the regulator located
before the main gas valves

On manifolds with a combination gas valve,

adjust the regulator under the brass cap on
the combination gas valve.

Measure the discharge temperature using a

thermometer. Laser thermometers are not as
accurate as a thermocouple type.

If the discharge ductwork outlet is hard to reach,

you may feed a thermocouple into the mixing tube
inside the blower discharge.

OPEN VALVE

GAS TYPE: NATURAL
MAX. TEMP. RISE: 140 F
DESIGN TEMP. RISE: 72 F
MAX. DISCHARGE TEMP.: 80
F

HIGH FIRE

HIGH FIRE

MR212

M511 & M611