Re-circulating damper control options, Manual positioning control (potentiometer), Two position control – FloAire FAV-M User Manual

Page 14: Static pressure control (photohelic)

Advertising
background image

14

Re-Circulating Damper Control Options

The Re-Circulating system is for controlling the amount of make-up air being brought into a building. It
can be set from a minimum 20& fresh air, and 80% return air to a maximum of 100% fresh air, and 0%
return air. The Re-Circulating dampers can be controlled by three different options.

Manual Positioning Control (Potentiometer)

The dampers can be control at a remote location by a manual potentiometer to any position from 20% to
100% fresh air. This will allow manually setting the dampers to match the building ventilation
requirements. It will take an extra 3 control wires at the remote location. On a power failure, or if the unit
of turned off, the return air damper will close by spring return.


Two Position Control

The dampers can be controlled by a two position switch (a field supplied switching device) to open the
fresh air to 100%. On opening of the circuit, power failure, or if the unit is shutoff, the return air damper
will close by spring return.

Static Pressure Control (Photohelic)

The dampers can be controlled by a building static pressure control. This controller will sense the
difference between pressure inside the building, and pressure outside the building (sensed at the A306
outdoor sensor), and position the dampers to maintain the pressure setting on the controller. The
controller has two set points and an indicator. The two set points are a minimum desired static pressure
point, and a maximum static pressure point.

The actual building static pressure will be shown by a visual indicator between these two settings. The
controller will modulate the dampers to maintain a static pressure between these set points.

When building static pressure is below the minimum setting, the damper motor will proportion open the
fresh air damper and close the return air damper until static increases above the minimum setting. At this
point, the damper motor will stop and hold this proportion.

If the building static continues to climb and goes above maximum setting, the damper motor will reverse
proportion, closing the fresh air damper and opening the return air damper until static drops below
maximum setting.

During the “OFF” or “Night” cycle of the unit, an internal switching circuit will close the return air damper.

See additional wiring and installation information on the static pressure controller and A306 outdoor
sensor. The static pressure controller can be ordered to be shipped loose or mounted inside the unit to
reduce field wiring and assembly.


Advertising
This manual is related to the following products: