TEMPERATURE CONTROL SYSTEMS

401M

The 401M replaces building-exhaust air with tempered make-up air.

A discharge-sensing controller that compensates for intake air temperature changes modulates
the burner flame.

A manual, remote SUMMER/OFF/WINTER selector switch controls the unit’s operation.

o

Summer: blower only operation.

o

Winter: blower and burner operation.

402M

The 402M is used primarily in door-heater applications. Its space override and low-limit
thermostat raise the discharge-air temperature when needed to maintain temperature in loading
dock areas.

A discharge sensor and remote controller modulate the burner flame to heat loading-dock door
areas.

A space thermostat overrides the set-point and increases the discharge-air temperature if warmer
air is needed in the total area.

A manual, remote SUMMEROFF/WINTER selector switch controls the unit’s operation.

o

Summer: blower only operation.

o

Winter: blower and burner operation.

403M

The 403M replaces building-exhaust air and maintains a constant space temperature.

A modulating space thermostat adjusts the burner to maintain the supply-air temperature
necessary to compensate for changes in the building heat losses and gains.

High- and low-discharge controllers limit the maximum and minimum temperature of the supply
air the unit delivers.

A manual, remote SUMMER/OFF/WINTER selector switch controls the unit’s operation.

o

Summer: blower only operation.

o

Winter: blower and burner operation.

404M

The 404M replaces building-exhaust air and maintains a constant space temperature, day or
night. During day operation, a modulating-space thermostat adjusts the burner to maintain the
supply-air temperature necessary to compensate for changes in building heat losses and gains.

High- and low-discharge controllers limit the maximum and minimum temperature of the supply
air the unit delivers.

During night operation, a space thermostat cycles the unit ON or OFF to maintain the space
temperature. The high-discharge sensor controls the discharge temperature during the night
cycle.

The unit’s operation is controlled by a manual remote SUMMER/OFF/WINTER selector switch.

o

Summer: blower-only operation.

o

Winter: blower and burner operation.

The electronic time clock changes the space-temperature control from the day thermostat to the
night thermostat.