6. When airflow switch (PS-01) is proven, the flame relay (RE-07) is energized through the high-

temperature limit control (TS-04), the optional low- and high-gas pressure switches (PS-03 & PS-04),
and the burner ON/OFF intake air stat (TS-06), if equipped. The pilot valve (VA-03) opens, and the
ignition transformer (TR-03) energizes

7. After the flame rod (SN-02) proves flame, the main valves (VA-01 & VA-02) open, and the ignition

transformer de-energizes

8. The temperature control systems amplifier (AM-01), monitors the discharge air sensor (TS-01) and

the remote discharge air set-point (TS-08), and modulates DC voltage to the modulating valve (VA-
05) to maintain discharge temperature

RCS

System

Minimum Outdoor

Air Temperature

(TS-10)

Minimum Indoor
Air Temperature

(TS-09)

Maximum Re-

Circulation

Percentage

Maximum

Discharge

Temperature

RCS5

-30

̊

F

7

̊

F

60%

90

̊

F

RCS10

-30

̊

F

25

̊

F

50%

120

̊

F

RCS15

-25

̊

F

58

̊

F

80%

90

̊

F

RCS20

-25

̊

F

54

̊

F

60%

120

̊

F

RCS25

-20

̊

F

55

̊

F

50%

140

̊

F

RCS30

-15

̊

F

47

̊

F

60%

120

̊

F

RCS35

0

̊

F

52

̊

F

80%

90

̊

F

RCS40

0

̊

F

35

̊

F

50%

140

̊

F