Burner troubleshooting chart, Proper spark gap – FloAire FAV-M User Manual

Page 31

Advertising
background image

31

Burner Troubleshooting Chart

Problem

Potential Cause

Corrective Action

Pilot does not light/stay lit

Main gas is off

Open main gas valve.

Air in gas line

Purge gas line.

Dirt in pilot orifice

Clean orifice with compressed air.

Gas pressure out of range

Adjust to proper gas pressure.

Pilot valve is off

Turn pilot valve on.

Leaking pilot orifice fitting

Tighten pilot orifice.

Excessive drafts

Re-direct draft away from unit.

Safety device has cut power

Check limits and airflow switch.

Dirty flame sensor

Clean flame sensor.

Remote panel in “Vent” mode

Change to “Heat” mode.

No spark at igniter

Check wiring, sensor, and ignition
controller. Check spark gap as shown
below.

Main burner does not light
(Pilot is lit)

Defective valve

Replace combination valve.

Loose valve wiring

Check wiring to valve.

Defective pilot sensor

Replace pilot sensor.

Shut-off valve closed

Open shut off valve.

Defective flame safety controller

Replace flame safety controller.

Pilot fails as main gas valves open
and main gas begins to flow

Plug the first burner port next to the
pilot gas tube with burner cement.

Not enough heat

Main gas pressure too low

Increase main gas pressure – do not
exceed 14 in. w.c. inlet pressure (5 psi.
on size 4-5 heater).

Too much airflow

Decrease airflow if possible.

Burner undersized

Check design conditions.

Gas controls not wired properly

Check wiring.

Thermostat setting too low

Increase thermostat setting.

Thermostat malfunction

Check/replace thermostat.

Unit locked into low fire

Check wiring.

Too much heat

Defective modulating gas valve

Check/replace modulating valve.

Thermostat setting too high

Decrease thermostat setting.

Unit locked into high fire

Check wiring.

Thermostat wired incorrectly

Check thermostat wiring.

Proper Spark Gap

Advertising
This manual is related to the following products: