Setting Low Fire

Use the Maxitrol amplifier to override the heater into low

fire.

Remove the 24V power source from amplifier

Adjust the low fire setting on the modulation valve so

the flame is 2-3 inches without dark spots

See the details for the low fire pressure adjustment

locations

Use the burner observation port on the end of the

unit to view the flame size

Replace all amplifier wires in the place they were

removed to set high and low fire

Additional capacity is provided via a low fire bypass

when MR212 low fire capacity is insufficient. Additional
adjustment is made via the R400S regulator installed in
the low fire bypass.





Final Start-Up

Set the Burner Intake On-Off Thermostat to the desired setting

This will automatically open the burner circuit when the outside air is above the selected

temperature

Turn the blower and burner service switches OFF

Now the unit will be operated from the control panel only

Operate the unit from the remote panel checking the lights, switches, set-points, and optional

thermostats or timers

Review the proper operation and sequence of operation with the customer to ensure that the unit is

operated properly and that the customer does not misuse the equipment

Complete the Start-Up Sheet and fax it to the service department to validate the warranty


Start-Up Complete

LOW FIRE

M511 & M611

LOW FIRE

MR212