Maxitrol series 44 troubleshooting – FloAire FAV-M User Manual

Page 38

Advertising
background image

38

Maxitrol Series 44 Troubleshooting

Symptom

Possible Cause

Field Test

Remedy

No gas flow

Modulating valve installed
improperly

Arrow in side of valve should
point in direction of gas flow.

Install properly

Continuous low fire
(electronics problem)

No voltage to amplifier


Short in modulator coil circuit





Short in TS144 circuit






Defective amplifier

Check for 24-v ac at amplifier
terminals 8 and 9

Remove wires connected to
amplifier terminals 6 and 7;
measure resistance
MR212: 60 – 80 ohms
M611 & M511: 45 to 55 ohms

Remove wires connected to
amplifier terminals 1, 2, and
3. Measure resistance across
wires 1 and 3, then across 2
and 3. Meter should read
greater than 2500 ohms.

Follow procedures in the
preliminary circuit analysis
section

Provide 24-v ac to
amplifier

If proper resistance
values are not observed;
replace modulator head
or repair wiring.


If readings are incorrect,
replace the TS114 or
repair wiring.




After following the
preliminary circuit
analysis test without
satisfactory results, the
amplifier can be
assumed defective.
Install replacement.

Continuous low fire
(electronics OK)

Open in modulator coil circuit





Plunger missing, jammed or
improperly installed

Remove wires connected to
amplifier terminals 6 and 7
measure resistance
MR212: 60 – 80 ohms
M611 & M511: 45 to 55 ohms

Inspect: plunger should
operate freely in solenoid
sleeve.

If proper resistance
values are not observed,
replace modulator head
or repair wiring


Clean or replace plunger
if necessary

Incorrect minimum fire

Incorrect by-pass metering
valve adjustment

Excessive negative burner
pressure

Re-set low fire (see start-up
instructions)

Close main-gas supply and
measure manifold pressure
with blower opening. Reading
should be less than 1.5-in wc
negative pressure.

Adjust to proper low fire


If reading is greater than
1.5-in wc negative
pressure, check for
clogged filters or other
inlet air restrictions.

Continuous minimum
discharge temperature

Defective amplifier



Short in T244 or TS244/TD244
circuit

Refer to the preliminary circuit
analysis section


Remove wires to amplifier
terminals 4 and 5. Set T244
or TD244 to maximum setting.
Measure resistance across
wires. Meter should read
6000 ohms +- 1000 ohms. If
TS244/TD244 are used, meter
should read 4500 ohms +-
1000 (TS244) and 2100 ohms
+- 150 (TD2440)

If amplifier is proven
defective, install
replacement

If reading is incorrect,
replace T244,
TS244/TD244 or repair
wiring

Advertising
This manual is related to the following products: