Setting High Fire – Manifold Pressure Method

Turn the burner service switch ON
Open the Burner Gas Shut Off Valve


Use the Maxitrol Amplifier to override the heater into

high fire.

On the A1014 amplifier remove the #4 wire
On the A1044 amplifier remove the #2 and #4 wire
On the M-Series adjust the set-point to be 160 F

Adjust the manifold gas pressure to achieve the desired

manifold pressure

See the details for the high fire pressure adjustment

locations.

On manifolds with an MR212 modulation valve,

adjust the small regulator inside the MR212
modulation valve

On manifolds with either an M511 or M611

modulation valve, adjust the regulator located
before the main gas valves

On manifolds with a combination gas valve, adjust

the regulator under the brass cap on the combination gas valve.

The manifold pressure can be read at the 1/4” pressure tap located after the modulating gas valve.

GAS TYPE: NATURAL
MAX. TEMP. RISE: 140 F
DESIGN TEMP. RISE: 72 F
MAX. DISCHARGE TEMP.: 80
F

OPEN VALVE

HIGH FIRE

HIGH FIRE

MR212

M511 & M611