If the pressure drop is too low, in fresh and

return air mode, add more blank-off panels to

the burner profile opening and bypass fresh air

and return air damper, which will increase the

pressure drop. (There must be at least 2 inches

of area minimum around the burner.) If the

correct air flow pressure drop is still not

achieved adjust the blower drives to increase

the blowers RPM.

If the pressure drop is too high, in fresh mode

only, remove or adjust the bypass damper

blank-off panels, which will decrease the

pressure drop. The return air damper opening

may need to be adjusted to maintain the correct

air flow pressure drop when switching back to

return air mode.

If the pressure drop is too high, in return air

mode only, remove or adjust the return air

damper and burner profile opening blank-off

panels, and add the blank-off panels to the

bypass damper, which will decrease the

pressure drop.