Symptom

Possible Cause

Field Test

Remedy

Incorrect minimum or
maximum discharge
air temperature

Improper TS144 location




Incorrect discharge air
temperature control calibration

Compare sensed temperature
at TS144 with average
discharge air temperature


Refer to the preliminary circuit
analysis section

Move TS144 to location
where average
temperature can be
sensed

If proper temperatures
are not observed, refer
to control calibration of
this manual

Continuous high fire
(electronics problem)

Open in TS144 circuit

Remove wires to amplifier
terminals 1, 2, and 3.
Measure resistance between
terminals 1 and 3, then
between terminals 2 and 3.
Meter should read greater
than 2500 ohms

If readings are incorrect,
replace TS114 or repair
wiring

Continuous high fire
(electronics OK)

Foreign material holding valve
open


Plunger jammed

Remove bottom plate and
inspect valve and seat


Inspect: plunger should be
smooth and clean, and
operate freely in solenoid
valve

Clean and replace valve
and seat. Replace if
necessary

Clean, or if necessary,
replace plunger

Incorrect high fire

Inlet pressure too low






Incorrect outlet pressure
adjustment

With heater operating at full
fire, take pressure reading at
inlet to modulation valve.
Pressure should meet or
exceed the units minimum gas
pressure

Read outlet pressure using a
manometer and compare with
recommendation of unit
capacities

Increase inlet pressure if
possible, or change to a
larger modulation valve.
Contact manufacturer for
increasing valve size.


See control calibration of
this manual

Continuous maximum
discharge air
temperature

Defective amplifier


Open in T244 or TS244/TD244










Incorrect space temperature
control calibration

Refer to the preliminary circuit
analysis section

Remove wires to amplifier
terminals 4 and 5. Set T244
or TD244 to maximum setting.
Measure resistance across
wires. Meter should read
6000 ohms +- 1000 ohms. If
TS244/TD244 are used, meter
should read 4500 ohms +-
1000 (TS244) and 2100 ohms
+- 150 (TD2440)

See control calibration section
of this manual

Replace amplifier if
defective

If reading is incorrect,
replace T244,
TS244/TD244 or repair
wiring







If proper action is
obtained, see calibration
section of this manual