Jaguar Caravan Multiple and Cascading Boilers

11

Figure 6. Alternative multiple side wall air intake & exhaust venting.

Note:

• Air intake opening must be 12 inches minimum above snow line or grade if it does not snow in

area boilers are located.

• No minimum horizontal distance between outlets or inlets.

• Exhaust termination to extend beyond air intake, prevent condensation from falling onto air intake

** Knowledge of local conditions will reveal the maximum height that repeated snowfalls

accumulate to. This height should be used as the snow line.

**

**