17

GAS PIPING

This section contains sizing and construction recommendations

for fuel supply piping to Caravan gas-fired modular boiler sys-

tems. Gas-fired equipment must conform not only to codes of

local regulatory agencies, but also to additional specifications that

may be imposed by the utility or gas supplier. Therefore, the fol-

lowing information should be considered only as a guideline.

Figure 6 illustrates a typical gas supply line installation. It consists

of a main between the utility’s meter box and the boiler system, a

main shut-off valve sediment trap, gas header pipe and drip legs

on individual boilers.

Individual gas lines to individual boiler modules should be equal

to or greater than the boilers supplied gas connection diameter.

Size of gas main and header pipes depends on volume of gas

required and acceptable pressure drop between meter and mod-

ules gas regulator valves. Minimum pressure required at each

valve is 3 inches of water column for natural gas measured while

all boilers and other gas-fired equipment on the same meter are

firing. Final pressure of gas header must vary no more than +0.3

in. of water column.

Gas main sizing

To determine the correct pipe diameter for the gas main serving a

specific Caravan system, proceed as follows:

a. Follow the building plans, find total length of straight pipe

between supply from gas meter and boiler gas header.

b. Using data in Table 2, calculate equivalent linear length of

screw pipe fittings used in fabrications of main. Add this to

figure from step (a) to obtain equivalent total length.

c. Find Caravan gas consumption in cubic feet per hour from

Table 1.

d. Multiply the system total hourly gas consumption by flow

correction value from local utility. If not available, use

1000 btu/cu.ft. (correction value = 1)

e. Locate system’s total equivalent pipe length in Table 3.

f.

Move vertically to the system’s corrected flow rate calculated

in step (c). If this value falls between two of those listed,

selected larger value.

g. From this point move horizontally to the left column and read

suggested pipe diameter for gas main.

Table 2. Equivalent linear length in feet of standard iron pipe fittings for natural gas

Number

of boilers

Cubic feet

per hour

2

780

3

1170

4

1560

5

1950

6

2340

7

2730

8

3120

Table 1. Gas consumption rate.

Pipe

Size

Inches

Elbow

Valve

Return

Bend

Side

Outlet

Tee

Standard

Medium

Sweep

Long

Sweep

Gate

Globe

Angle

1/2

3/4

1

1-1/4

1-1/2

2

3

0.84

1.17

1.57

2.19

2.63

3.55

5.72

0.52

0.73

0.98

1.37

1.64

2.23

3.59

0.41

0.57

0.77

1.07

1.29

1.74

2.81

0.031

0.044

0.057

0.082

0.098

1.320

2.130

2.50

3.50

4.68

6.54

7.84

10.60

17.08

1.12

1.84

2.11

2.94

3.52

4.77

7.69

1.25

1.75

2.34

3.27

3.92

5.30

8.84

1.66

2.33

3.11

4.35

5.21

7.05

11.40

9. GAS LINE SIZING AND LAYOUT