Jaguar Caravan Multiple and Cascading Boilers

34

ERROR CODE

INDICATION

REMEDY

30

Excess Flue Temperature

Check flue gas temperature, at the maximum firing
rate and high water temperature. If the flue gas
temperature reaches 212˚F, check the fuel input
rate and combustion. Check the condition of the
heat exchanger. If the flue gas temperature does
not reach 212˚F, replace the flue sensor.

31

Low Water Cutoff Error

If a low water cutoff is installed, check the system
water pressure and correct. Check the condition of
the LWCO. If no LWCO is installed, check the
jumper is in place at the wiring terminal board.
See Figure 14.

32

Excess Water Inlet Temperature

Check that the wire harnesses to the water inlet
and outlet sensors are not reversed. The water
inlet sensor harness should have a blue colored
connector, the water outlet sensor harness should
have a red colored connector. Check that the
pumping flow direction is correct.

51

Reset Button Error

Try turning power supply off and on again. If error
returns, replace the display board.

52

Boiler Model Selection Error

Check that the proper boiler model selection and
confirmation code is entered in the display.
See Table 4.

continued from page 24

04

Domestic Hot Water Tank Sensor Open

If sensor is utilized, check wire harness connections
going to the sensor, or replace the sensor. If no sen-
sor is utilized, check the proper DHW mode is pro-
grammed. See Table 4.

14

Domestic Hot Water Tank

Sensor Shorted

If sensor is utilized, replace the sensor. If no sensor
is utilized, check the proper DHW mode is pro-
grammed. See Table 4.

6.3

WARNING ERRORS:

Indicated by an “H” in the mode display. Operation of the space heating mode is not

affected, and the warning is displayed intermittently. Operation of the DHW mode is automatically restored,
once the condition is fixed. The temperature display shows the error code. Pressing the “reset” button is
not required.