Jaguar caravan multiple and cascading boilers 14, Boiler pressure drop – Slant/Fin Jaguar User Manual

Page 14

Advertising
background image

Jaguar Caravan Multiple and Cascading Boilers

14

7. CONDENSATE REMOVAL SYSTEM

The Jaguar J-390C boiler is equipped with a built-in condensation

drain and trap system. This system consists of two traps, one

being dedicated to the condensate produced by the boiler, and

another being dedicated to the condensate produced within the

vent piping. Both of these traps must be filled with water. This is

most easily accomplished by pouring water from a small container

into the vent connector at the top of the boiler, before the vent pipe

is attached, until the tubing loop trap in the rear of the boiler is vis-

ibly filled. DO NOT operate the boiler without filling the trap with

water to prevent flue gas discharge into space. Periodic inspection

should be made of this assembly for deterioration of the tubing

and components, and to insure that the traps are not plugged. If

any part is plugged or appears to have excessive sediment within,

it should be removed from the drain assembly, have the obstruc-

tion cleared, refilled with water and reinstalled as before.

A 3/4” PVC tee assembly, located in the rear of the boiler jacket, is

provided to run the condensate liquid from the boiler. Connect the

plastic tubing that will be run to the drain to the bottom take-off of

the tee. Leave the top take-off of the tee open, to act as a vacuum

breaker. If the building drain is above the bottom portion of the tee,

a condensate removal pump will be required. This pump must

have an overflow switch, and be compatible with the acidic con-

densate liquid, as must all fittings and the tubing used in this con-

densate removal system. (See Figure 9).

No part of the condensate removal system can be exposed to

freezing temperatures, or any other conditions that could cause

blockage. DO NOT run drain tubing to the outside of the building.

In addition, certain jurisdictions or drain pipe materials may require

a neutralization unit to be installed in the condensate removal sys-

tem. Any piping other than plastic types will be subject to corrosion

or deterioration from the acidic condensate, which may have a pH

level as low as 3.0. A condensate filter containing lime, marble, or

phosphate chips can neutralize the condensate to a pH level

above 6.5, which is safe for all drain piping materials. (See Figure

9). The neutralizing filter medium will require periodic changing, to

ensure it’s affectiveness. Replacing the medium on an annual

basis is recommended, or refer to the manufacturer’s instructions

for systems that are available for neutralizing condensate.

COMMONWEALTH OF MASSACHUSETTS SPECIAL
REQUIREMENT

When the Jaguar J-390C is installed and used in the
Commonwealth of Massachusetts, a neutralization unit MUST be
installed in the condensate removal system.

8. WATER PIPING AND

Jaguar Multiple Boiler Systems utilize primary/secondary piping.
Jaguar boilers require a minimum of 17.5 gallons per minute water
flow rate. A primary loop circulator is factory supplied with each
Jaguar boiler, this circulator should be used in the boilers primary
loop. Listed below is a chart listing the Jaguar boiler’s pressure
drop based on GPM flow rate, this chart also lists water tempera-
ture rise based on maximum gas input.

PIPING AND WATER FLOW

Good system design addresses flow rates through boilers. It is

possible to have too little flow and too much flow. Most boiler sys-

tem designs are based on a 20˚F to 30˚F temperature rise in the

boiler when it is firing at full input.

When the flow rate is too high through a module the water flow

tends to short circuit from the return tapping to the supply tapping

of a module. When flow rate is too high the boiler efficiency may

drop and there is excess electrical consumption by the circulator.

Primary/secondary piping is required for multiple Jaguar boilers.

This method ensures that each boiler will receive the same inlet

water temperature, and only the boilers that are firing will have

water flowing through them. Each boiler must have a dedicated

circulator piped on it’s primary loop. See figures 10 and 11 for the

location of components and piping layout.

If isolation valves are installed in the individual boiler piping to the

common headers, a dedicated manual reset low water cutoff and

manual reset high limit must be installed on each boiler’s piping,

as close to the boiler as possible and beneath the isolation valves.

See figures 10 and 11.

The primary loop must have its own pump, water that is flowing in

the primary loop will not flow into the secondary circuit

NEUTRALIZING UNIT (IF REQUIRED)

CONDENSATE PUMP (IF REQUIRED)

DRAIN INSIDE BUILDING

PLASTIC TUBING

DRAIN VACUUM BREAKER, LEAVE OPEN

Figure 9. Condensate disposal system

Flow

Rate

(gpm)

Temp

Rise

(˚F)

Boiler

Head

Loss

(Feet w.c.)

28.0

25˚

16

23.5

30˚

11.5

20.0

35˚

8.5

17.5*

40˚

7.0

Boiler Pressure Drop

* Minimum flow rate recommended.

Jaguar Multiple Boiler

System may be piped

using Slant/Fin supplied

headers or by using field

piped primary boiler

loops.

Advertising