Slant/Fin Jaguar User Manual

Page 18

Advertising
background image

Jaguar Caravan Multiple and Cascading Boilers

18

FROM

HEADER

3 1/4”

TYP

Figure 12.Typical gas supply installation for Jaguar boiler.

Nominal

Iron Pipe

Size Inches

Internal

Diameter

Inches

Equivalent Length of Pipe, Feet

10

20

30

40

50

60

70

80

90

100

125

150

175

200

1/2

3/4

1

1-1/4

1-1/2

2

2-1/2

3

4

.622

.844

1.049

1.380

1.610

2.067

2.469

3.068

4.026

132

278

520

1,050

1,600

3,050

4,800

8,500

17,500

92

190

350

730

1,100

2,100

3,300

5,900

12,000

73

152

285

590

890

1,650

2,700

4,700

9,700

63

130

245

500

760

1,450

2,300

4,100

8,300

56

115

215

440

670

1,270

2,000

3,600

7,400

50

105

195

400

610

1,150

1,850

3,250

6,800

46

96

180

370

560

1,050

1,700

3,000

6,200

43

90

170

350

530

990

1,600

2,800

5,800

40

84

160

320

490

930

1,500

2,600

5,400

38

79

150

305

460

870

1,400

2,500

5,100

34

72

130

275

410

780

1,250

2,200

4,500

31

64

120

250

380

710

1,130

2,000

4,100

28

59

110

225

350

650

1,050

1,850

3,800

26

55

100

210

320

610

980

1,700

3,500

Table 3.

Gas main sizing guide

Maximum capacity of pipe in cubic feet gas per hour for gas pressure of 0.5 psig or less and a pressure drop

of 0.3 inch water column (based on a 0.60 specific gravity gas).

Advertising