Jaguar Caravan Multiple and Cascading Boilers

2

1. INTRODUCTION

If additional information is desired please contact your local
Slant/Fin Sales Representative or Slant/Fin Technical Services.
Slant/Fin may be found on the web at www.slantfin.com

This application manual is intended to provide the piping and control
method for applying multiple Jaguar J-390C boilers to a space heat-
ing and domestic hot water heating system. Use this manual, in
conjunction with the Jaguar J-390C Installation and Operating
Instructions, publication J-40.

The following sections of the Installation and Operating Instructions
(J-390C) must be adhered to:
1. Boiler location and foundation
2. Clearances to combustibles
3. Contamination prevention
4. Air supply and ventilation
5. Venting application and materials*
6. Water treatment
7. Condensate disposal
8. Operating instructions
9. Care and Maintenance

*Common venting of these appliances is not permitted. Direct vent
terminals cannot be clustered together or stacked vertically. Direct
vent terminals can be mounted side by side horizontally, provided
there is a 12" minimum distance between them.

There are two methods available to control J-390C Caravan boilers:
1. Jaguar link method to operate up to 8 boilers. An optional system

sensor is required for operation of this method. Supply water
system sensor (Part no. 833433000) max be ordered to
Slant/Fin boiler distributor.

2. External signal (0-10 Vdc input). Control such as Tekmar control

265 or 275 (operates up to 4 boilers). Energy Management
System may be used with this method. One optional interface
control is required for operation of each boiler in the system.
Part number for interface control kit is 830130000.

Jaguar boilers may also be used in a heating system with a
Caravan cast iron modular boiler system. Since high efficiency con-
densing boilers only condense when the return water temperature is
low, around 130 F or lower, it makes sense to use a lower cost
Caravan cast iron boiler at higher water temperature. We call a com-
bination Caravan Cast Iron Modular Boiler used in a system with a
Jaguar Multiple Boiler a “Hybrid Boiler System”. We address Hybrid
Boiler Systems within this manual.

Model

No.

Water

Content

(gal.)

Ship

Wt.

Lbs.

Vent

Conn

Air

Intake.

Water

Correction

at Boiler

Space

Btwn.

Boilers

**

Length

with

Header

**

Min.

Header

Size

J-390C 2B

J-390C 3B

J-390C 4B

J-390C 5B

J-390C 6B

J-390C 7B

J-390C 8B

4

6

8

10

12

14

16

600

900

1200

1500

2340

2730

3120

4"

4"

4"

4"

4"

4"

4"

4"

4"

4"

4"

4"

4"

4"

1-1/4

1-1/4

1-1/4

1-1/4

1-1/4

1-1/4

1-1/4

3-1/4

3-1/4

3-1/4

3-1/4

3-1/4

3-1/4

3-1/4

50-1/2"

77-3/4"

104-1/4"

131-1/8"

158"

184-7/8"

211-3/4"

2"

2"

3"

3"

3"

3"

3"

Table 1: Gas multiple boiler ratings and dimension/hot water model 50 psi maximum working pressure

2. RATINGS AND DIMENSIONS

Model

No.

Consists of

CSA Input

(MBH)

CSA output

(MBH)

I=B=R Net

(MBH)

Combustion

Efficiency

Boiler

Horse-

Power

No. of Htg.

Boiler

Boiler

Model No.

Max

Min

Max

Min

Max

Min

Max

Min

J-390C 2B

J-390C 3B

J-390C 4B

J-390C 5B

J-390C 6B

J-390C 7B

J-390C 8B

2

3

4

5

6

7

8

J-390C

J-390C

J-390C

J-390C

J-390C

J-390C

J-390C

780

1170

1560

1950

2340

2730

3120

110

110

110

110

110

110

110

704

1056

1408

1760

2112

2464

2816

106

106

106

106

106

106

106

612

918

1224

1530

1836

2142

2448

92

92

92

92

92

92

92

91.6

91.6

91.6

91.6

91.6

91.6

91.6

96.7

96.7

96.7

96.7

96.7

96.7

96.7

21

31.5

42

52.6

63.1

73.6

84.1

System Turndown

Model

No.

Turndown

Ratio

J-390C 2B

J-390C 3B

J-390C 4B

J-390C 5B

J-390C 6B

J-390C 7B

J-390C 8B

7 to 1

10.6 to 1

14.2 to 1

17.7 to 1

21.3 to 1

24.8 to 1

28.4 to 1

** “Length with headers allows for 3 1/4" between boiler.