CIRCUIT BREAKERS AND WIRING SELECTION

Breakers and Gauge of the wires used in the installation must be rated to drive current values as indicated in below tables.
NOTE every country could have local electrical requirements and regulations. If local electrical regulations require higher rates
than values suggested in this section please follow local directives.

1 PHASE:

1 PHASE INPUT

1 PHASE OUTPUT

EXT. BATT

MODELO

L1-L2 in Parallel

L1-L2 in Parallel

Ext. Batt.

120Vac 120Vac

120Vdc

6KVA 2Ph

8AWG or thicker

63 Amp

8AWG or thicker

63 Amp

10AWG or thicker

50 Amp

(curve D)

(curve D)

(curve C)

10KVA 2Ph

6AWG or thicker

125 Amp

6AWG or thicker

125 Amp

10AWG or thicker

50 Amp

(curve D)

(curve D)

(curve C)

2 PHASES:

2 PHASES INPUT

2 PHASE OUTPUT

EXT. BATT

MODELO

L1-N L2-N

L1-N

L2-N

Ext.

Batt.

120Vac 120Vac

120Vac

120Vac

120Vdc

6KVA 2Ph

10AWG or

thicker

32 Amp

10AWG or

thicker

32 Amp

10AWG or

thicker

32 Amp

10AWG or

thicker

32 Amp

10AWG or thicker

50 Amp

(curve D)

(curve D)

(curve D)

(curve D)

(curve C)

10KVA 2Ph

8AWG or

thicker

63 Amp

8AWG or

thicker

63 Amp

8AWG or

thicker

63 Amp

8AWG or

thicker

63 Amp

10AWG or thicker

50 Amp

(curve D)

(curve D)

(curve D)

(curve D)

(curve C)

IMPORTANT: When using 2 separate outputs, each individual output drives only 50% of total UPS capacity. For
example: for 6KVA UPS, Max. output 1 is 3KVA and Max output 2 is 3KVA.

IMPORTANT: Before connecting 2 outputs in parallel is mandatory to check both outputs are in phase (0º). This
parameter is configured through menu by LCD and front panel. Check installation section in this manual.

IMPORTANT: If external battery cabinets are connected to UPS, it is necessary to install one DC breaker
between UPS and each external battery cabinet. Original External Battery cabinets normally include its own
input breaker.


WARNING: The correct wire gauge or section is strongly affected by diverse factors such as: Operation temperature, wire
length, type of wire and kind of installation. UPS user and/or his electrical contractor must assure an appropriate selection for
wire and protection devices for complying with local regulations and directives for electrical installations.
Wiring colors must be selected according to local directives and regulations

LEAK CURRENT PROTECTION

In many countries, now a day, it is legally required to install protections against current leakage to protect human beings in
cases of leaks o discharges to ground. It is responsibility of the end user and/or electrical contractor selecting and including
these protection devices in the electrical circuit of the UPS.