20140714_ 6K-10K 2PH (EN)

- 14

CONFIGURATION 1: UPS 1Phase (1 Input 120Vac - 1 Output 120Vac)

** 1 phase output can supply 100% of total UPS capacity.

WARNING:
** To connect 2 outputs in one phase output we must be sure phase angle between outputs is 0º and only 1
phase line must be connected at UPS input. Please follow below procedure:


MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE


1.- Make sure L1 and L2 terminals at input terminal block are connected with a jumper.
2.- UPS must be connected to one phase input line only.
3.- Check to confirm function 03 in LCD panel is configured as “ATO” (automatic mode). In this mode, inverter output will
follow input phase. Phase angle read by UPS must be 000 in function 03 screen. “ATO” is factory preconfigured value.
4.- Check to confirm function 04 in LCD panel is configured as “ENA” (Enabled). If not, error alarms 1A and 1B will be
generated by the UPS. Note: “ENA” is the factory preconfigured value.













** Detailed instructions to check and configure function 03 & 04 available in Configuration section