- UPS ONLINE 6K/10K 2Ph

ENGLISH

_____________________________________________________________________________________________________________________

20140714_ 6K-10K 2PH (EN)

- 6

2.

AVAILABLE

MODELS

6K-EX

2Ph

&

10K-EX

2Ph

UPS with internal batteries and connection for external battery cabinets to increase backup time.

EX:

Indicates connection for external batteries

2PH:

Indicates 2 Phases product.

Model Internal

Batteries

Ext.

Batt. Connector

Isolation Transformer

6KEX / 10KEX 2Ph

Y Y No

EXTERNAL

BATTERIES


2Ph models can operate with internal batteries but if extended backup time is required external batteries can be connected to
UPS.

External Battery Cabinet for 6K / 10K 2Ph:
Model: EX-BAT-T6/T10

2PH

Batteries: 40 pieces x 12V-9AH: 4 groups of 10 batteries in parallel.
DC Voltage:

120Vdc

WARNING

External battery packs for 2PH models is not compatible with other 6K / 10K models. UPS 6K and 10K 2Ph

require 120Vdc external battery packs.

Some other 6K and 10KVA models require 240Vdc external battery packs.

Make sure you will connect compatible external battery pack to your UPS to avoid permanent damages not

covered by warranty.