09: Frequency range for ECO mode

Interface Setting

Parameter 2: Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.

Parameter 3: Set high frequency point for ECO mode.

50 Hz: Setting range is from 52.0Hz to 54.0 Hz.

60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.

10: Bypass mode setting

Interface Setting

Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass mode depending on
bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected neither manual nor automatic Bypass

mode will not be available under any situations.

Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is available when required.
DIS: Bypass disabled to work in following manner:
* Automatic bypass is available for overload or error causes
* Manual bypass is NOT allowed. Manual bypass means users can force to Bypass
mode when pressing OFF button in front panel.
If ENA is set UPS will go to bypass mode when OFF button is selected by user.
If DIS was set UPS will Turn OFF when OFF button is selected.

11: Battery backup time setting

Interface Setting

Parameter 3:

000~999: Set the maximum backup time from 0min to 999min. UPS will shut down
to protect battery after backup time arrives. The default value is 990min.

DIS:
Disable battery discharge protection and backup time will depend on battery
capacity. UPS will be working in battery mode until low battery level is detected.

12: Neutral Line Loss

Interface Setting

Parameter 2:
N.L: Indicates Neutral Loss Detection Function

Parameter 03:
Can be configured as: DIS, ATO or CHE
DIS: Disable: UPS will not check for input neutral connection
ATO: Automatic: UPS will detect input neutral connection.
If detected no action is required.

If NOT detected: Alarm is generated. If UPS is turned on with this condition it will
turn on in battery mode.
When neutral is detected UPS will go back to normal AC mode and alarm will be
muted automatically.
CHE: Works similar to ATO but after neutral is detected UPS will not go to normal
AC mode automatically. User action is required to mute alarm and put UPS in
normal mode. Manual action is to enter in this menu for selecting CHE value to

make a manual neutral search by pressing enter twice.
ATO is pre-configured value at factory.

13: DC battery voltage meter calibration

Interface Setting

Battery DC value indicated on LCD can be calibrated by this function. This
function does not changes real battery charger output. Only LCD value.
Parameter 2:
Select “Add” or “Sub” function to adjust battery voltage to real figure.
Parameter 3: the voltage range is from 0V to 9.9V, the default value is 0V.