20140714_ 6K-10K 2PH (EN)

- 12

4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK

AC

LINES

CONNECTION

PROCEDURE

• Make sure the UPS is Off before starting the installation.
• Remember to check all wires to be connected are not powered (including external batteries).


UPS terminal block preparation

Remove cover of terminal block at the UPS rear panel, identified as 12 in rear panel section of this manual
DO NOT use a wall power outlet to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power

6KVA UPS. UPS Input wire must be connected by breaker protected line to electric panel board.

UPS Input and Output Connection

Connect input and output ground wires to proper place on the UPS chassis on both sides of terminal blocks. Ground wires
must be FIRST to be connected and LAST to be disconnected.
Connect UPS input and output wires according to your UPS model or configuration as described in following figures:

AVAILABLE

CONFIGURATIONS

This equipment can offer 3 different connection configurations:

1.- One Phase Input 120Vac – One Phase Output 120Vac:

1 x Input Line to Neutral Voltage: 120Vac
1 x Output Line to Neutral Voltage: 120Vac

2.- Two Phases Inputs 120Vac – Two Phases outputs 120Vac:

2 x Input Line to Neutral Voltage: 120Vac
2 x Output Line to Neutral Voltage: 120Vac

2.- Two Phases Inputs 120vac – One Phase output 208Vac:

2 x Input Line to Neutral Voltage: 120Vac
1 x Output Line to Neutral Voltage: 208Vac