User manual, English – XMART Optima 10K 2PH User Manual

Page 38

Advertising
background image

User Manual

- UPS ONLINE 6K/10K 2Ph

ENGLISH

_____________________________________________________________________________________________________________________

20140714_ 6K-10K 2PH (EN)

- 38

Configuration

menu

functions

and

screens

01: Output Voltage Configuration

LCD

Parameter 3: Output Voltage Value
Output can be selected from following options:
100: 100Vac
110: 110Vac

115: 115Vac
120: 120Vac
127: 127Vac
Default is 120Vav

02: Output Frequency

LCD

60 Hz, CVCF mode

50 Hz, Normal mode

ATO

Parameter 2: Output Frequency
Output can be selected from following choices:
50.0Hz: 50.0Hz.
60.0Hz: 60.0Hz.
ATO: Automatic: Under this mode output frequency is selected according to input
frequency:

50Hz if input is (46Hz y 54Hz) and
60Hz if input is (56Hz y 64Hz).
ATO mode is factory default value.

Parameter 3: Frequency Mode
Adjusting parameter 3, can be selected CF Mode which is frequency converter mode or
NCF in NON converter mode.

CF: This mode allows fixing a fixed output frequency in parameter 2.
NCF: This mode allows output frequency was selected according to the input meanwhile
input frequency is inside allowed range. If input frequency is out of range UPS will go to
battery mode.

IMPORTANT NOTE ABOUT FREQUENCY CONVERSION FUNCTION "CF":

* When CF function is enable to generate an output with a different frequency value than input, bypass mode will be
automatically disable.
* When CF function is activated, maximum power output is de-rated to 60% of standard power output. For example: for
10KVA UPS when CF is activated max. output power is 6KVA.

03: Output Phase

LCD

Parameter 2: Constant Output Phase

CP:

Sets UPS to CP mode. If selected, the output phase will be fixed at 0, 120, 180 or

240 according to setting in parameter 3. No matter input phase.
SPECIAL NOTE: if CP is activated all BYPASS modes are disabled. We suggest to
keep this function configured as ATO.
CP mode is used when 2 alternative input sources operates with different phase
angle as explained in section 04 (special mode for motor-generators)

ATO:
In this mode output phase angle will be fixed according to the input phase angle
detected when UPS starts up.


Parameter 3: Phase setting

In CP mode:
You may select the phase angle between output lines.
In ATO mode: parameter 3 shows phase angle saved as read in the input when UPS
was powered up.

Advertising