- UPS ONLINE 6K/10K 2Ph

ENGLISH

_____________________________________________________________________________________________________________________

20140714_ 6K-10K 2PH (EN)

- 22

PARALLEL CONFIGURATION 2: 2 INPUT - 2 OUTPUTS

- 2 INPUTS 120Vac

- 2 OUTPUTS 120Vac

** Each output can supply only 50% of total UPS capacity.

WARNING:
To use this UPS as 2 phases UPS is MANDATORY to check there is NO jumpers connected between L1 and L2
at Input and output terminal block. You must follow below instructions:

MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE IN YOUR UPS AND SYSTEM


1.- Remove all jumpers between L1 and L2 at input and output terminal block.
2.- You MUST confirm Configuration MENU 03 and 04 in LCD panel are configured as follows:
2.1- Configuration MENU 03 must be set as “ATO” (automatic mode): Output phase angle is same than input phase
angle. In normal conditions angle phase between separate phases is 120º.
2.2- Configuration MENU 04 is not available under this mode. It is indicated as RESERVED. Since UPS detects input has
been wired as 2 separate phases, output cannot be configured as 1 phase output.










** Detailed instructions to check and configure function 03 & 04 available in Configuration section




Only after configuring all UPS to be connected in parallel, terminal block connections can be done according to following
figure: