- UPS ONLINE 6K/10K 2Ph

ENGLISH

_____________________________________________________________________________________________________________________

20140714_ 6K-10K 2PH (EN)

- 13

SIMPLIFIED INTERNAL BLOCK AND AC TERMINAL BLOCKS

WARNING

If UPS will work in 1phase input - 1 phase output configuration, output L1 and L2 must be connected by a jumper (J2) in
output terminal block. Under this configuration inputs L1 – L2 MUST be connected with a jumper (J1). If not, under
bypass mode, input L1 and L2 will be short-circuited.
Additionally functions 03 and 04 in LCD front panel MUST be revised and properly configured. Check terminal block
configuration in this section.

WARNING

Configurable functions 03 and 04 of the configuration menu available on LCD must be revised and properly configured
according to the output mode selected.
Revise Installation section and Configuration section of this manual.

WARNING

WRONG INPUT OR OUTPUT CONNECTION MAY PRODUCE PERMANENT DAMAGE OF THIS PRODUCT OR YOUR SYSTEM.
THIS KIND OF DAMAGE IS NOT COVERED BY THE WARRANTY.