EXTERNAL BATTERY CABINETS – CONNECTION PROCEDURE

UPS Tower type

WARNING

Make sure EXBATT model to be connected is compatible with UPS model. For 2Ph 6K and 10K UPS models, battery pack
voltage is 120Vdc Measure and verify DC voltage supplied by battery pack before making connections.

1.- Check all DC breakers are in OFF position

2.- Remove all DC connector covers in UPS and EXBATT cabinets

3.- Using appropriate cable (supplied with the EXBATT) connect UPS with EXBATT 1. In case of more than 1 EXBATT connect

EXBATT 1 with EXBATT 2 and so on until last EXBATT.

4.- Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries.