User manual, English, Error / failure codes on lcd – XMART Optima 10K 2PH User Manual

Page 43: Alarm codes on lcd

Advertising
background image

User Manual

- UPS ONLINE 6K/10K 2Ph

ENGLISH

_____________________________________________________________________________________________________________________

20140714_ 6K-10K 2PH (EN)

- 43

ERROR / FAILURE CODES ON LCD

ERROR

CODE

ERROR

DESCRIPTION

ICON

BEEP ALARM

01

Bus failure detected when starting

Continuous Beep

02

Hi BUS Voltage

03

Low BUS Voltage

04

Bus Unbalanced

06

Converter Over Current

11

Inverter soft start failure

12

Inverter HI voltage

13

Inverter LOW voltage.

14

Inverter L1 output short-circuit

SHORT

15

Inverter L2 output short-circuit

SHORT

17

L1-L2 Inverter output (line to line) short circuit detected.

SHORT

1A

L1 Negative Voltage failure

1B

L2 Negative Voltage failure

21

Battery SCR Short-Circuit

24

Inverter Relay Short-Circuit

29

Battery fuse broken in battery mode

31

Failure detected in parallel communication

36

Parallel output unbalanced

41

HIGH Temperature.

43

UPS Overload: High power consumption in Watts at UPS
output.

OVERLOAD

46

Not Recognized UPS model. Check jumper configuration in
CRTL board.


ALARM

CODES

ON

LCD

WARNING

CODE

WARNING

DESCRIPTION

01

Battery unconnected

02

IP Neutral loss or IP L2 fuse broken

07

Battery over charge

08

Low battery

09

Overload

0A

Fan failure

0B

EPO enable

0D

Over temperature

0E

Charger failure

10

L1 IP fuse broken

11

L2 IP fuse broken

21

Different Line setting in parallel UPS

22

Different Bypass setting in parallel UPS

24

Different configuration for Inverter output in parallel UPS

25

Different configuration for frequency in parallel UPS

27

Different configuration for L1 and L2 in parallel UPS

28

Different configuration for phase angle in parallel UPS

33

Locked in bypass after overload 3 times in 30min

34

Converter current unbalance

35

Battery fuse broken

36

Inverter inter-current unbalance

39

Input phase error

3A

Cover of maintain switch is open

3C

Utility extremely unbalanced

Advertising