Step 7 — Orifice Change

— This unit is factoiy as­

sembled for heating operation using natural gas at an elevation
from sea level to 2000 ft. Tliis unit uses orifice type
LH32RFnnn, where “nnn” indicates the orifice size based on
drill size diameter in thousands of an inch.

HIGH ELEVATION (Above 2000 ft) — Use accessoiy high
altitude kit when installing tliis unit at an elevation of 2000 to
7000 ft. For elevations above 7000 ft, refer to Table 2 to identi­
fy the correct orifice size for fhe elevafion. See Table 3 for the
number of orifices required for each unit size. Purchase these
orifices from your local Carrier dealer. Follow instmctions in
accessoiy Installation Instmctions to install the correct orifices.

Table 2 — Altitude Compensation*

ELEVATION (ft)

NATURAL GAS ORIFICEf

Low Heat

High Heat

0-1,999

30

29

2,000

30

29

3,000

31

30

4,000

31

30

5,000

31

30

6,000

31

30

7,000

32

31

8,000

32

31

9,000

33

31

10,000

35

32

*As the height above sea level Increases, there is less oxygen per

cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes. Includes a 4% input reduction per each 1000 ft.

fOrifices available through your Carrier dealer.

Table 3 — Orifice Quantity

UNIT

ORIFICE QUANTITY

48TJD016

5

48TJD020,
48TJD024,
48TJD028,

48TJF016

48TJF020,
48TJF024,
48TJF028

7

CONVERSION TO LP (Liquid Propane) GAS -- Use acces­
soiy LP gas conversion kit when converting this unit for use
witli LP fuel usage for elevations up to 7000 ft. For elevations
above 7000 ft, refer to Table 4 to identify the correct orifice
size for tlie elevation. See Table 3 for the number of orifices
required for each unit size. Purchase these orifices from your
loctil Carrier dealer. Follow instmctions in accessoiy Installa­
tion Instmctions to install the correct orifices.

Table 4 — LP Gas Conversion*

ELEVATION (ft)

LP GAS ORIFICEf

0-1,999

36

2,000

37

3,000

38

4,000

38

5,000

39

6,000

40

7,000

41

8,000

41

9,000

42

10,000

43

*As the height above sea level increases, there is less oxygen per

cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes. Includes a 4% input reduction per each 1000 ft.

fOrifices available through your Carrier dealer.