Table 12 — economi$erlv sensor usage – Carrier 48TJ016-028 User Manual

Page 25

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

ECONOMISERIV STANDARD SENSORS

Outdoor Air Temperature (OAT) Sensor — The outdoor air
temperature sensor (HH57AC074) is a 10 to 20 mA device
used to measure the outdoor-air temperature. The outdoor-air
temperature is used to determine when the EconoMi$erIV can
be used for free cooling. Tire sensor must be field-relocated.
See Fig. 32. The operating range of temperature measurement

is 40 to 100 F.

Supply Air Temperature (SAT) Sensor — The supply air
temperature sensor is a 3 K tirennistor located at the inlet of the

indoor fan. See Fig. 33. This sensor is factoiy installed. The op­

erating range of temperature measurement is 0° to 158 F. See
Table 11 for sensor temperature/resistance values.

Tire temperature sensor looks like an eyelet terminal with

wires innning to it. Tire sensor is located in the “crimp end”
and is settled from moisture.

Low Temperature Compressor Lockout Switch — The
EconoMi$erIV is equipped with an ambient temperature lock­
out switch located in the outdoor airstretun which is used to

lockout the compressors below a 42 F ambient temperature.

See Fig. 32.

Table 11 — Supply Air Sensor Temperature/

Resistance Values

Table 12 — EconoMI$erlV Sensor Usage

TEMPERATURE (F)

RESISTANCE (ohms)

-58

200,250

_40

100,680

-22

53,010

-4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3.000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

ECONOMf$ERIV CONTROL MODES

IMPORTANT: Tire optiontil EconoMi$er2 does not include

a controller. Tire EconoMi$er2 is operated by a 4 to 20 mA
signal from an existing field-supplied controller (such as
PremierLink'*''* control). See Pig. 36 for wiring infonnation.

Detennine the EconoMi$erlV control mode before set up of

the control. Some modes of operation may require different sen­

sors. Refer to Table 12. The EconoMi$erl V is supplied from the
factoiy with a supply air temperature sensor, a low temperature

compressor lockout switch, and an outdoor air temperature

sensor. TIris allows for operation of the EconoMi$erTV with

outdoor air diy bulb changeover control. Additional accesso­
ries can be added to ttllow for different types of changeover
control and operation of the EconoMi$er!V and unit.

APPLICATION

ECONOMISERIV WITH OUTDOOR AIR

DRY BULB SENSOR

Accessories Required

Outdoor Air

Dry Bulb

None. The outdoor air dry bulb sensor

is factory installed.

Differential Dry Bulb

CRTEMPSN002A00*

Single Enthalpy

HH57AC078

Differential Enthalpy

HH57AC078

and

CRENTDIF004A00*

CO

2

tor DCV Control

using a Wall-Mounted

CO

2

Sensor

33ZCSENC02

CO

2

for DCV Control

using a Duct-Mounted

CO

2

Sensor

33ZCSENC02f

and

33ZCASPC02**

GC

0

CRCBDIOX005A00tt

’CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on

many different base units. As such, these kits may contain parts that

will not be needed for installation.

t33ZCSENC02 is an accessory CO

2

sensor.

**33ZCASPC02 is an accessory aspirator box required for duct-

mounted applications.

tfCRCBDIOXOOSAOO is an accessory that contains both 33ZCSENC02

and 33ZCASPC02 accessories.

Outdoor Diy Bulb Changeover — The standard controller is
shipped from the factoiy configured for outdoor diy bulb
changeover control. The outdoor air and supply air temperature
sensors tU'e included as standai'd. Por this control mode, the
outdoor temperature is comptiied to an adjustable set point se­
lected on the control. If the outdoor-air temperature is above
tlie set point, tlie EconoMi$erIV will adjust the outdoor-air
dampers to minimum position. If the outdoor-air temperature is
below tlie set point, the position of the outdoor-air dampers will
be controlled to provide free cooling using outdoor tdr. When
in this mode, the LED next to the free cooling set point potenti­
ometer will be on. The changeover temperature set point is
controlled by the free cooling set point potentiometer located
on the control. See Pig. 37. The settle on the potentiometer is A,
B, C, and D. See Fig. 38 for the corresponding temperature
changeover values.
Differential Dry Bulb Control — For differential diy bulb
control tire standard outdoor diy bulb sensor is used in conjunc­
tion with an additional accessoiy return air sensor (part number
CRTEMPSN002A00). The accessoiy sensor must be mounted
in the return airstream. See Fig. 39.

In this mode of operation, the outdoor-air temperature is

compared to the return-air temperature and the lower tempera­
ture airstream is used for cooling. When using this mode of
changeover control, turn tlie free cooling/enthalpy set point
potentiometer fully clockwise to the D setting. See Fig. 37.

EXHAUST

FAN SETPOINT

LED LIGHTS

WHEN EXHAUST

CONTACT IS MADE

Ml

POSITION SETTING

MAXIMUM DAMPER

DEMAND CONTROL

VENTILATION SETPOINT

LED LIGHTS WHEN

DEMAND CONTROL

VENTILATION INPUT

IS ABOVE SET POINT

NIMUM DAMPER-----------------—-ЛИИ

iSITIOM SETTING

-fat—

р

ША-,

DEMAND CONTROL

VENTILATION SETPOINT

Ik

'O

LED LIGHTS WHEN

OUTDOOR AIRIS

SUITABLE FOR

FREE COOLING

FREE COOLING/ENTHALPY

CHANGEOVER SET POINT

Fig. 37 — EconoMi$erlV Controller Potentiometer

and LED Locations

25

Advertising