Carrier 48TJ016-028 User Manual

Page 32

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 14 — Fan Performance — 48TJD016 (Low Heat Units)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIHFLOW

(cfm)

0.2

0.4

0.6

0.8

1.0

1,2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

809

1.53

1317

906

1.74

1502

994

1.96

1690

1078

2.18

1882

1156

2.41

2077

1230

2.64

2275

4800

850

1.76

1516

942

1.98

1706

1027

2,20

1899

1107

2.43

2094

1183

2.66

2293

1255

2.89

2495

5100

892

2.01

1733

979

2.24

1928

1061

2.46

2125

1138

2.70

2325

1211

2.93

2528

1281

3.17

2733

5400

934

2.28

1970

1017

2.52

2169

1096

2.75

2371

1170

2.99

2575

1241

3.22

2781

1309

3.47

2990

5700

976

2.58

2225

1058

2.82

2429

1132

3.06

2635

1204

3.30

2843

1272

3.54

3053

1338

3.79

3266

6000

1019

2.90

2500

1096

3.14

2709

1168

3.38

2919

1238

3.63

3131

1304

3.88

3345

1368

4.13

3562

6300

1063

3.24

2795

1136

3.49

3008

1206

3.74

3223

1273

3.99

3439

1337

4 24

3657

6600

1106

3.61

3111

1177

3.86

3329

1244

4.11

3547

1309

4.37

3767

6900
7*5 fin

1150

4.00

3448

1218

4.26

3670

7500

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(cfm)

1.4

1.6

1.8

1.9

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

1301

2.87

2477

1369

3.11

2683

1434

3.35

2891

1497

3.47

2997

1497

3.60

3103

4800

1324

3.13

2700

1390

3.37

2909

1454

3.62

3120

1515

3.74

3226

1515

3.87

3334

5100

1349

3.41

2942

1413

3.66

3153

1475

3.90

3367

1535

4.03

3475

1535

4.16

3584

5400

1374

3.71

3202

1437

3.96

3416

1498

4.21

3633

5700
6000
6300

nRfin

1402

4.04

3481

1463

4.29

3699

_

_

_

_

6900
7200
7500

LEGEND

Bhp

— Brake Horsepower

Flop

— Factory-Installed Option

Watts

— Input Watts to Motor

NOTES:

1, Standard low-medium static drive range is 891 to 1179 rpm (for 208/230

and 460-v units) or 1159 to 1429 rpm (for 575-v units). Alternate high-
static drive range is 1227 to 1550 (for 208/230 and 460-v units). The
alternate high-static drive is not available for 48TJ016 575-v units. Other

rpms require a field-supplied drive.

2.

Maximum continuous bhp is 4.25 (208/230 and 460 v) or 3.45 (575 v)

and the maximum continuous watts are 3775 (208/230 and 460 v) or
3065 (575 v). Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.

3.

Static pressure losses (i.e., economizer) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5.

Fan performance is based on wet coils, clean filters, and casing losses.

See Tables 21-23 for accessory/FlOP static pressure information.

6.

Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi­

dence. Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

7.

Use of a field-supplied motor may affect wiring size. Contact your Carrier

representative for details.

Table 15 — Fan Performance — 48TJD020 and 024 (Low Heat Units)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIHFLOW

(cfm)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Walts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

755

2.27

1908

831

2.58

2171

901

2.91

2443

968

3,24

2723

1031

3.58

3009

1091

3.93

3302

6,000

810

2.72

2287

881

3.04

2556

947

3.37

2833

1010

3.71

3116

1070

4.05

3406

1127

4.40

3702

6,500

866

3.22

2710

932

3.55

2985

994

3.88

3266

1054

4.23

3554

1111

4.57

3847

1166

4.93

4146

7,000

923

3.78

3177

985

4.11

3458

1044

4.45

3744

1100

4.80

4036

1155

5.15

4333

1207

5.51

4635

7,500

980

4.39

3690

1038

4.73

3976

1094

5.07

4267

1148

5.43

4564

1200

5.78

4864

1250

6.15

5170

8,000

1038

5.06

4251

1093

5.40

4542

1146

5.75

4838

1197

6.11

5138

1246

6.47

5443

1294

6.84

5752

8,500

1096

5,78

4859

1148

6.13

5156

1198

6.49

5456

1247

6,85

5761

1294

7.22

6070

1340

7.59

6382

9,000

1154

6,56

5517

1204

6.92

5818

1251

7.28

6123

1298

7.65

6432

1343

8.02

6745

1388

8.40

7062

9,500

1213

7,40

6224

1260

7.77

6531

1306

8.13

6840

1350

8.51

7154

1394

8.88

7471

1436

9.26

7791

10,000

1272

8.30

6983

1317

8.67

7294

1360

9.05

7608

1403

9.43

7926

1445

9.81

8247

1486

10.19

8570

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(cfm)

1.4

1.6

1.8

1.9

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

1149

4.28

3602

1204

4.65

3907

1258

5.02

4217

1284

5.20

4375

1309

5.39

4533

6,000

1183

4.76

4003

1236

5.13

4310

1288

5.50

4622

1313

5.68

4780

1337

5.87

4939

6,500

1219

5.29

4450

1270

5.66

1459

1320

6.03

5073

1344

6.22

5232

1368

6.41

5391

7,000

1258

5,88

4942

1307

6.25

5253

1355

6.62

5569

1378

6.81

5729

1402

7.00

5890

7,500

1299

6.52

5480

1346

6.89

5794

1392

7.27

6113

1415

7.46

6273

1437

7.65

6435

8,000

1341

7.21

6065

1387

7.59

6383

1392

7.97

6704

1453

8.16

6866

1475

8.36

7028

8,500

1385

7.97

6699

1429

8.35

7019

1472

8.73

7343

1493

8.93

7506

1514

9.12

7670

9,000

1431

8.78

7382

1473

9.15

7705

1515

9.55

8032

1535

9.75

8196

9,500

1478

9.65

8114

1519

10.04

8441

10,000

LEGEND

Bhp

— Brake Horsepower

Flop

— Factory-Installed Option

Watts

— Input Watts to Motor

NOTES:

1.

Standard low-medium static drive range for the 020 size is 910 to

1095 rpm. Standard low-medium static drive range for the 024 size is
1002 to 1225 rpm. Alternate high-static drive range for the 020 size is
1069 to 1287. Alternate high-static drive range for the 024 size is 1193 to
1458 rpm. Other rpms require a field-supplied drive.

2.

Maximum continuous bhp for the 020 size is 5.90. Maximum continuous

bhp for the 024 size is 8.7 (208/230, 575 v) or 9.5 (460 v). The maximum

continuous watts for the 020 size is 5180. The maximum continuous
watts for the 024 size is 7915 (208/230, 575 v) or 8640 (460 v). Do not

adjust motor rpm such that motor maximum bhp and/or watts is

exceeded at the maximum operating cfm.

3.

Static pressure losses (i.e., economizer) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5.

Fan performance is based on wet coils, clean filters, and casing losses.

See Tables 21-23 for accessory/FlOP static pressure information.

6.

Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi­

dence. Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

7.

Use of a field-supplied motor may affect wiring size. Contact your Carrier

representative for details.

32

Advertising