Carrier 48TJ016-028 User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

T T P ( 4 1 P L C S ^

0 ' - 3 ? / 8 '

1 3/8* 8iA. 08AIM HOLE

UNIT

STD UNIT

WEIGHT

ECONOMIZER

WEIGHT

CORNER

A

CORNER

B

CORNER

C

CORNER

D

DIMA

DIM B

DIMC

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

ft-in.

mm ft-in.

mm

tt-in.

mm

48TJD,

TJF024

1850

839

90

41

443

201

406

184

476

216

525

238

3-2

965

3-5

1041

1-8

508

48TJD,

TJF028

2000

907

90

41

471

214

428

194

526

239

574

260

3-2

965

3-5

1041

1-8

508

NOTES:
1. Refer to print for roof curb accessory dimensions.

2, Dimensions in ( ) are in millimeters.

3^ Center of Gravity.

Direction of airflow.

5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:

• Rear: 7'-0" (2134) for coil removal. This dimension can be reduced to

4'-0" (1219) if conditions permit coil removal from the top.

• 4'-0" (1219) to combustible surfaces, all four sides (includes between

units).

' Left side: 4'-0" (1219) for proper condenser coil airflow.
' Front: 4'-0" (1219) for control box access.
• Right side: 4'-0" (1219) for proper operation of damper and power

exhaust if so equipped.

• Top: 6'-0" (1829) to assure proper condenser fan operation.
' Bottom: 14" (356) to combustible surfaces (when not using curb).
' Control box side: 3'-0" (914) to ungrounded surfaces, non-combustible.
• Control box side: 3'-6" (1067) to block or concrete walls, or other

grounded surfaces.

• Local codes or jurisdiction may prevail.

7. With the exception of clearance for the condenser coil and the damper/

power exhaust as stated in Note #6, a removable fence or barricade
requires no clearance.

8. Dimensions are from outside of corner post. Allow O'-^/ie" (8) on each

side for top cover drip edge.

SECTfON A-A

Fig. 5 — Base Unit Dimensions; 48TJ024,028