Table 16 — Fan Performance — 48TJD028 (Low Heat Units)

AVAiLABLE EXTERNAL STATIC PRESSURE (in. wg)

AIHFLOW

(cfm)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

941

3.35

2769

1002

3.80

3140

1061

4.27

3528

1117

4.76

3934

1171

5.27

4356

1224

5.80

4794

7,500

999

4,05

3348

1057

4.53

3742

1112

5,02

4152

1166

5.54

4579

1218

6,07

5020

1268

6.63

5478

8,000

1058

4.85

4007

1113

5.35

4424

1165

5.87

4856

1216

6.41

5304

1266

6.97

5766

1314

7.55

6243

8,500

1117

5.74

4750

1169

6.28

5190

1219

6.83

5645

1268

7.40

6114

1315

7.98

6597

1361

8.58

7094

9,000

1177

6.75

5583

1226

7.31

6047

1274

7.89

6524

1320

8.48

7015

1365

9.09

7520

1410

9.72

8037

9,500

1237

7.98

6511

1284

8.46

6999

1329

9.07

7499

1374

9.69

8012

1417

10.33

8538

1459

10.98

9076

10,000

1297

9.12

7450

1342

9.74

8051

1385

10.37

8574

1428

11,02

9110

1469

11.68

9657

1510

12.36

10217

10,500

1358

10.49

8674

1400

11.14

9209

1442

11.80

9755

1483

12,47

10314

1523

13.16

10883

11,000

1418

12.00

9919

1459

12.67

10478

_

_

_

_

_

_

_

_

_

_

_

_

11,250

1449

12.80

10585

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIHFLOW

(cfm)

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

1274

6.35

5248

1323

6.92

5718

1371

5.54

6204

7,500

1316

7.20

6960

1364

7.79

6437

1410

6.41

6939

8,000

1360

8.14

6734

1406

8.76

7239

1450

7.40

7759

8,500

1406

9.20

7605

1449

9.83

8129

1492

8.48

8666

9,000

1453

10.36

8568

1495

11.02

9111

1536

9.69

9667

9,500

1501

11.64

9627

1541

12.32

10190

10,000

_

_

_

_

_

_

_

_

_

10,500

_

_

_

_

_

_

_

_

_

11,000

11,250

LEGEND

Bhp

— Brake Horsepower

Flop

— Factory-Installed Option

Watts

— Input Watts to Motor

NOTES;

1.

Standard low-medium static drive range Is 1066 to 1283 rpm. Alternate

high-static drive range is 1332 to 1550. Other rpms require a field-
supplied drive.

2.

Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (460 v) and

the maximum continuous watts are 9510 (208/230, 575 v) or 11,000
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or
watts is exceeded at the maximum operating cfm.

3. Static pressure losses (i.e., economizer) must be added to external static

pressure before entering Fan Performance table,

4. Interpolation is permissible. Do not extrapolate.
5.

Fan performance is based on wet coils, clean filters, and casing losses.

See Tables 21-23 for accessory/FlOP static pressure information,

6.

Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi­
dence. Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

7. Use of a field-supplied motor may affect wiring size. Contact your Carrier

representative for details.

Table 17 — Fan Performance — 48TJF016 (High Heat Units)

AVAILABLE EXTERNAL STATIC PRESSURE (iri. wg)

AIHFLOW

(cfm)

0.2

0.4

0,6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

819

1.55

1335

914

1.76

1518

1001

1.98

1705

1083

2.20

1894

1160

2.42

2088

1234

2.65

2284

4800

861

1.78

1538

951

2.00

1726

1035

2.22

1916

1113

2.45

2110

1188

2.68

2307

1259

2.91

2507

5100

904

2,04

1759

989

2,26

1952

1069

2,49

2147

1145

2,72

2345

1218

2.95

2545

1287

3.17

2749

5400

947

2,32

1999

1028

2,55

2197

1105

2,78

2396

1179

3,01

2598

1248

3.25

2802

1315

3.49

3009

5700

990

2,62

2259

1068

2,85

2461

1142

3,09

2665

1213

3,33

2871

1280

3.57

3079

1345

3.81

3289

6000

1034

2.94

2539

1109

3.18

2745

1180

3.42

2953

1248

3.67

3163

1313

3.91

3375

1376

4.16

3589

6300

1078

3.29

2840

1150

3.54

3050

1218

3.78

3262

1284

4.03

3476

1348

4.28

3692

_

_

_

6600

1123

3.67

3161

1192

3.91

3376

1258

4.16

3592

6900

1167

4.06

3504

1234

4.32

3723

7200

AVAILABLE EXTERNAL STATIC PRESSURE (irt. wg)

AIHFLOW

(cfm)

1.4

1.6

1.8

1.9

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

1304

2,88

2484

1371

3,12

2688

1435

3.36

2895

1467

3.48

2999

1497

3.60

3104

4800

1327

3.14

2711

1393

3.38

2917

1456

3.62

3126

1486

3.75

3232

1517

3.87

3338

5100

1353

3.43

2955

1417

3.67

3165

1478

3.92

3377

1508

4.04

3484

1537

4.16

3592

5400

1380

3.73

3219

1442

3.98

3432

1502

4.23

3646

1531

4.35

3755

5700
6000
6300

1408

4.06

3503

1468

4.31

3718

-

-

-

6600
6900
7200

-

-

-

LEGEND

Bhp

— Brake Horsepower

Flop

— Factory-Installed Option

Watts

— Input Watts to Motor

NOTES:

1

Standard low-medium static drive range is 891 to 1179 rpm (for 208/230
and 460-v units) or 1159 to 1429 rpm (for 575-v units). Alternate high-
static drive range is 1227 to 1550 (for 208/230 and 460-v units). The
alternate high-static drive is not available for 48TJ016 575-v units. Other
rpms require a field-supplied drive.
Maximum continuous bhp is 4.25 (208/230 and 460 v) or 3.45 (575 v)

and the maximum continuous watts are 3775 (208/230 and 460 v) or

3065 (575 v). Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.

3. Static pressure losses (i.e., economizer) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5.

Fan performance is based on wet coils, clean filters, and casing losses.

See Tables 21-23 for accessory/FlOP static pressure information.

6.

Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi­
dence. Using tan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

7. Use of a field-supplied motor may affect wiring size. Contact your Carrier

representative for details.