Legend and notes for fig. 58 and 59 – Carrier 48TJ016-028 User Manual

Page 47

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

LEGEND AND NOTES FOR FIG. 58 AND 59

LEGEND

AHA

— Adjustable, Heat Anticipator

SN

— Sensor

BKR W/AT

— Breaks with Amp Turns

TB

— Terminal Block

C

— Contactor, Compressor

TC

— Thermostat Cooling

CAP

— Capacitor

TH

— Thermostat Heating

CB

— Circuit Breaker

TRAN

— Transformer

CC

— Cooling Compensator

CLO

— Compressor Lockout

COMP

— Compressor Motor

DM

— Damper Motor

DU

— Dummy Terminal

EQUIP

— Equipment

FPT

— Freeze Protection Thermostat

FU

— Fuse

GND

— Ground

HPS

— High-Pressure Switch

lAQ

— Indoor Air Quality Sensor

IDM

— Induced-Draft Motor

IFM

— Indoor-Fan Motor

IGC

— Integrated Gas Unit Controller

L

— Light

LED

— Light Emitting Diode

LPS

— Low-Pressure Switch

LS

— Limit Switch

MGV

— Main Gas Vaive

NEC

— National Electrical Code

OAT

— Outdoor Air Temperature Sensor

OCCUP

— Occupancy Sensor

OFC

— Outdoor-Fan Contactor

OFM

— Outdoor-Fan Motor

PL

— Plug Assembly

PMR

— Phase Monitor Relay

QT

— Quadruple Terminal

RAT

— Return Air Temperature Sensor

RS

— Rollout Switch

<; >

Terminal (Marked)

Q

Terminal (Unmarked)

I I

Terminal Block

9

Splice

----------- Factory Wiring

Field Control Wiring

---------- Accessory or Optional Wiring

To indicate common potential only;
not to represent wiring.

°' °

Economizer Motor

— R e m o t e POT Field Accessory

;

OAT Sensor

Disch Air Sensor

; RAT Accessory Sensor

Low Ambient Lockout Switch

NOTES:

1. Compressor and/or tan motor(s) thermally protected three phase motors protected against primary

single phasing conditions.

2. If any of the original wire furnished must be replaced, it must be replaced with Type 90° C or its

equivalent.

3. TRAN1 is wired for 230-v operation. If unit is 208 v, disconnect the black wires from the ORN TRAN

wire and reconnect to the RED TRAN wire. Apply wirenuts to wires.

4. CB1,2 Must Trip Amps are equal to or less than 156% FLA. IFCB 140%.
5. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices;

before replacing CLO check these devices.

6. Jumpers are omitted when unit is equipped with economizer.
7. Number(s) indicates the line iocation of used contacts. A bracket over (2) numbers signifies a single

pole, double throw contact. An underlined number signifies a normally closed contact. Plain (no line)
number signifies a normally open contact.

8. Remove Jumper between RC and RH.
9. 620 Ohm, 1 watt, 5% resistor should be removed only when using differential enthalpy or dry bulb.

10. If a separate field-supplied 24 v transformer is used for the lAQ sensor power supply, it cannot have the

secondary of the transformer grounded.

11. OAT sensor is shipped inside unit and must be relocated in the field for proper operation.
12. For field-installed remote minimum position POT. remove black wire jumper between P and PI and set

control minimum position POT to the minimum position.