Table 18 — Fan Performance — 48TJF020 and 024 (High Heat Units)

AVAILABLE EXTERNAL STATIC PRESSURE (iti, wg)

AiHFLOW

(cfm)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

795

2,43

2043

866

2.74

2306

934

3.07

2578

998

3.40

2856

1059

3.74

3142

1117

4.08

3434

6,000

854

2,92

2452

921

3.24

2722

984

3.57

3998

1044

3,90

3281

1102

4.25

3570

1158

4.60

3865

6,500

914

3,46

2909

977

3.79

3184

1036

4.12

3465

1093

4.46

3752

1148

4.81

4045

1201

5.16

4343

7,000

975

4.06

3414

1034

4.39

3695

1090

4.73

3981

1144

5.08

4272

1196

5.43

4569

1246

5.79

4870

7,500

1037

4.72

3969

1092

5.06

4255

1145

5.41

4546

1196

5.76

4842

1256

6.12

5142

1294

6.48

5447

8,000

1099

5,44

4575

1150

5,79

4866

1201

6.14

5162

1249

6.50

5462

1297

6,86

5766

1343

7.22

6075

8,500

1161

6,22

5232

1210

6,57

5529

1258

6.93

5829

1304

7.29

6134

1349

7,66

6443

1393

8.03

6755

9,000

1223

7,07

5943

1270

7,43

6245

1315

7.79

6550

1360

8.16

6869

1403

8.53

7171

1445

8.90

7487

9,500

1286

7,98

6708

1331

8.34

7014

1374

8.71

7324

1416

9.08

7638

1457

9.46

7954

1498

9.84

8274

10,000

1349

8.95

7528

1392

9.32

7839

1433

9.70

8154

1473

10.07

8471

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(cfm)

1.4

1.6

1.8

1.9

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

1173

4.44

3732

1227

4.80

4036

1279

5.17

4345

1304

5.35

4502

1329

5,54

4629

6,000

1211

4.95

4165

1263

5.32

4471

1313

5.69

4782

1337

5.87

4939

1361

6,06

5097

6,500

1252

5,53

4646

1302

5.89

4954

1350

6.26

5267

1373

6.56

5425

1396

6.64

5584

7,000

1295

6.16

5176

1343

6.52

5487

1389

6.90

5802

1412

7.09

5961

1434

7.28

6121

7,500

1340

6.85

5756

1386

7.22

6070

1431

7.60

6387

1452

7.79

6547

1474

7.98

6709

8,000

1388

7.60

6388

1431

7.97

6704

1474

8.35

7024

1495

8.54

7186

1516

8.74

7348

8,500

1436

8.41

7071

1478

8.79

7390

1520

9.17

7713

1540

9.37

7876

_

_

_

9,000

I486

9.28

7807

1527

9.67

8130

_

_

_

_

_

_

_

_

_

9,500

1538

10.22

8597

10,000

LEGEND

Bhp — Brake Horsepower
Flop — Factory-Installed Option

Watts

— Input Watts to Motor

NOTES;

1.

Standard low-medium static drive range for the 020 size is 910 to

1095 rpm. Standard low-medium static drive range for the 024 size is
1002 to 1225 rpm. Alternate high-static drive range for the 020 size is
1069 to 1287. Alternate high-static drive range for the 024 size is 1193 to
1458 rpm. Other rpms require a tield-supplied drive.

2,

Maximum continuous bhp tor the 020 size is 5.90. Maximum continuous

bhp for the 024 size is 8.7 (208/230, 575 v) or 9.5 (460 v). The maximum

continuous watts for the 020 size is 5180. The maximum continuous
watts for the 024 size is 7915 (208/230, 575 v) or 8640 (460 v). Do not

adjust motor rpm such that motor maximum bhp and/or watts is

exceeded at the maximum operating dm.

3.

Static pressure losses (i.e., economizer) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5.

Fan performance is based on wet coils, clean filters, and casing losses.

See Tables 21-23 for accessory/FlOP static pressure information.

6.

Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi­

dence. Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

7.

Use of a field-supplied motor may affect wiring size. Contact your Carrier

representative for details.

Table 19 — Fan Performance — 48TJF028 (High Heat Units)

AVAfLABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(cfm)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

992

4.05

3,348

1051

4.44

3,668

1106

4.83

3995

1160

5.24

4331

1212

5.65

4675

1262

6.08

5026

7,500

1055

4.77

3,947

1110

5.17

4,277

1162

5.58

4615

1214

6.00

4960

1263

6.43

5312

1311

6.86

5672

8,000

1118

5.58

4,610

1170

5.99

4,950

1220

6.41

5298

1268

6.84

5653

1315

7.27

6014

1361

7.72

6382

8,500

1182

6,46

5,339

1231

6.88

5,690

1278

7.31

6047

1324

7.75

6411

1369

8,20

6782

1413

8.66

7158

9,000

1246

7,42

6,136

1292

7.86

6,498

1337

8.30

6865

1381

8.75

7239

1424

9,21

7618

1466

9.68

8003

9,500

1310

8,47

7,005

1354

8.92

7,377

1397

9.38

7754

1439

9.84

8137

1480

10,31

8525

1520

10.79

8918

10,000

1374

9.61

7,947

1416

10.07

8,329

1457

10.54

8715

1497

11.02

9107

1537

11.50

9504

10,500

1439

10.84

8,964

1479

11.32

9,356

1518

11.79

9752

11,000

1503

12.17

10,059

1542

12.65

10,460

11,250

1536

12.86

10,636

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(cfm)

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

1311

6.51

5385

1359

6.96

5751

1405

6.00

6124

7,500

1358

7.30

6039

1403

7.76

6412

1448

6.84

6792

8,000

1406

8.17

6767

1560

8.63

7137

1492

7.75

7524

8,500

1456

9.12

7541

1498

9.59

7929

1539

8.75

8323

9,000

1507

10.15

8393

1548

10.63

8790

9,500

10,000

10,500

11,000

11,250

LEGEND

Bhp

— Brake Horsepower

Flop

— Factory-Installed Option

Watts

— Input Watts to Motor

NOTES:

1,

Standard low-medium static drive range is 1066 to 1283 rpm. Alternate

high-static drive range is 1332 to 1550. Other rpms require a field-

supplied drive.

2.

Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (460 v) and

the maximum continuous watts are 9510 (208/230, 575 v) or 11,000

(460 v). Do not adjust motor rpm such that motor maximum bhp and/or

watts is exceeded at the maximum operating cfm.

3.

Static pressure losses (i.e,, economizer) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5.

Fan performance is based on wet coils, clean filters, and casing losses.

See Tables 21-23 for accessory/FlOP static pressure information.

6.

Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi­

dence, Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.

7.

Use of a field-supplied motor may affect wiring size. Contact your Carrier

representative for details.

34