Table 5 — Electrical Data

UNIT
48TJ

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA

LRA

Qty

Hp

FLA (ea)

Hp

FLA

FLA

LRA

FLA

MCA

MOCP*

016

(15 Tons)

208/230

187

253

25.6

190

25.6

190

3

0.5

1.7

3.7

10.5/11.0

0.57

74/74

90/90

4,6

18.8

0.57

79/79

100/100

460

414

508

13.5

95

13.5

95

3

0.5

0.8

3.7

4.8

0.30

38

50

2.3

6.0

0.30

40

50

575

5f8

632

10.2

75

10.2

75

3

0.5

0.8

3.0

3.9

0.57

30

35

2.1

4.8

0.57

32

40

020

(18 Tons)

208/230

187

253

33

237

23

184

3

0.5

1.7

5.0

15,8/15.8

0.57

85/85

110/110

4.6

18.8

0.57

90/90

110/110

460

414

508

16.2

130

10.2

90

3

0.5

0.8

5.0

7.9

0.30

41

50

2,3

6.0

0,30

43

50

575

518

632

12.7

85

9

73

3

0.5

0.8

5.0

6,0

0.57

33

45

2,1

4.8

0.57

35

45

024

(20 Tons)

208/230

187

253

33

237

29.5

237

2

1

6.6

7.5

25.0/25.0

0.57

109/109

125/125

4,6

18.8

0.57

114/114

125/125

460

414

508

16.2

130

14.1

130

2

1

3.3

7.5

13.0

0.30

54

70

2,3

6.0

0.30

56

70

575

518

632

12.7

85

11.3

85

2

1

3.4

7.5

10.0

0.57

44

50

2.1

4.8

0.57

46

50

028

(25 Tons)

208/230

187

253

47.5

265

33

237

2

1

6.6

10.0

28.0/28.0

0.57

134/134

175/175

4.6

18.8

0.57

138/138

175/175

460

414

508

22.9

145

16.2

130

2

1

3.3

10.0

14.6

0.30

66

80

2.3

6.0

0.30

68

90

575

518

632

17.9

102

12.7

85

2

1

3.4

10.0

13.0

0.57

55

70

2,1

4.8

0.57

57

70

LEGEND

FLA

— Full Load Amps

HACR

— Heating, Air Conditioning and Refrigeration

!FH/l

~ Indoor (Evaporator) Fan Motor

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP

— Maximum Overcurrent Protection

NEC

— National Electrical Code

OFM

— Outdoor (Condenser) Fan Motor

RLA

— Rated Load Amps

'Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimofor and combinafion load

equipmenf (refer fo NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker, Canadian units may be
fuse or circuit breaker,

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage Is
greater than 2%. Use the following formula to determine the percent of volt­
age imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60.

ABC

AB = 452

V

BC = 464

V

AC = 455

V

Average Voltage ;

452 + 464 + 455

f37f

= 457

Determine maximum deviation from average voltage.

(AB) 457 - 452 = 5

V

(BC) 464 - 457 = 7 v
(AC) 457-455 = 2

V

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = f 00 x

457

= t .53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.

t o o

X

13