Fig. 36 — economiser2 wiring, Fig. 35 — economi$erlv wiring – Carrier 48TJ016-028 User Manual

Page 24

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

LEGEND

DCV

— Demand Controlled Ventilation

lAQ

— Indoor Air Quality

LALS

— Low Temperature Compressor

Lockout Switch

OAT

— Outdoor-Air Temperature

POT

— Potentiometer

Potentiometer Detault Settings:
Power Exhaust Middle
Minimum Pos,

DCV Max.
DCV Set
Enthalpy

Fully Closed
Middle
Middle

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the lAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3.

For field-installed remote minimum position POT, remove black wire jumper

between P and PI and set control minimum position POT to the minimum
position.

Fig. 35 — EconoMI$erlV Wiring

OAT

— Outdoor Air Temperature Sensor

NOTES:
1. Switch on actuator must be in run position for economizer to operate.

2. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

Fig. 36 — EconoMiSer2 Wiring