Table 1 — Physical Data (cent)

UNIT 48TJ

016D/F

020D/F

024D/F

028D/F

FURNACE SECTION

Rollout Switch Cutout Temp (F)+

190

190

190

190

Burner Orifice Diameter (in... .drill size)

Natural Gas

0.1285...30/0.136...29

0.1285...30/0.136...29

0.1285...30/0.136...29

0.1285...30/0.136...29

Thermostat Heat Anticipator Setting (amps)

208/230, 575

Stage 1

0.98

0.98

0.98

0.98

Stage 2

0.44

0.44

0.44

0,44

460

V

stage

1

0.80

0.80

0.80

0,80

Stage 2

0.44

0.44

0.44

0,44

Gas Input

Stage 1

172,000/225,000

206,000/270,000

206,000/270,000

206,000/270,000

Stage 2

230,000/300,000

275,000/360,000

275,000/360,000

275,000/360,000

Efficiency (Steady State) {%)

81

81

81

81

Temperature Rise Range
Manifold Pressure (in. wg)

15-45/20-50

15-45/20-50

15-45/20-50

15-45/20-50

Natural Gas

3.3

3.3

3.3

3.3

Gas Valve Quantity

1

1

1

1

Field Gas Connection Size (in

.-FPT)

3/4

3/4

3/4

3/4

HIGH-PRESSURE SWITCH (psig)

Cutout
Reset (Auto)__________________

426
320

LOW-PRESSURE SWITCH (psig)

Cutout
Reset (Auto)__________________

27
44

FREEZE PROTECTION THERMOSTAT (F)

Opens
Closes

30 ±5
45 ±5

OUTDOOR-AIR INLET SCREENS

Quantity...Size (in.)

Cleanable

2.. .20x25x 1

1.. .20x 20 x1

RETURN-AIR FILTERS

Quantity...Size (in.)

Throwaway*’'

4.. .20x20x2
4.. .16x20x2

POWER EXHAUST

V

2

Hp, 208/230-460

V

Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)

LEGEND

Bhp

™ Brake Horsepower

TXV

— Thermostatic Expansion Valve

'Circuit 1 uses the lower portion of condenser coil and lower portion of evap­

orator coils; and Circuit 2 uses the upper portion of both coils.

fRollout switch is manual reset.

**The 48TJ028 units requires 2-in. industrial-grade filters capable of handling

face velocities of up to 625 ft/min (such as American Air Filter no, 5700 or

equivalent).

NOTE: The 48TJ016-028 units have a low-pressure switch (standard) located
on the suction side.