Generac Power Systems 53187 User Manual

Page 112

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SECTION 5.2

ENGINE CRANKING SYSTEM

I

PARTS

ENGINE ELECTRICAL SYSTEM

Type 1 Engine Cranking System (Continued)

THE BATTERY (CONT’D):

2. Hold the current draw for 15 seconds. Then, observe
battery voltage. If the voltage remains at 9.6 volts or
more, the battery Is good. If battery voltage drops below
9.6, go to Step 3.
3. Connect the battery to a charger and set the charger

to Its fast charge rate. DO NOT EXCEED 40 AMPS.
After three (3) minutes, check the voltmeter reading. If
reading is greater than 16.5 volts, replace the battery.

If desired, the battery can be tested using an automo­

tive type battery hydrometer. Check the battery for both

(a) state of charge and (b) condition, as follows:

1.

Follow the hydrometer manufacturer’s instructions

carefully. Draw a sample of the battery fluid from each
battery cell, one cell at a time. Read the specific gravity
of the fluid, then return the fluid to the cell from which it
was drawn. As the specific gravity reading of the fiuid
from each ceil is taken, write the reading down.
2. If the hydrometer being used does not have a "Per­
centage of Charge scale, compare the readings with the

following:

SPECIRC GRAVITY

PERCENTAGE OF CHARGE

1.260

100%

TS’JS

TT553

55^5

T7T75

25%

3. If necessary, remove the battery and recharge it to a

100% state of charge.

4.

If the difference in specific gravity between the

highest and lowest reading cell is 0.050 (50 points) or
more, the battery is nearing the end of its useful life and
should be replaced.
5. If the highest reading obtained is less than 1.200,

recharge the battery then retest specific gravity, if the

difference between the highest and lowest reading is
still more than 0.050 (50 points), replace the battery.

10 AMP CIRCUIT BREAKER (CB3):

General: The 10 amp circuit breaker (CB3) is physi­

cally mounted on the generator control panel. It is
electrically connected in series with the battery power
supply to the engine control circuit board. Should the
circuit breaker trip open due to an overload, or if it is set
to its OFF or OPEN position, engine cranking and
startup cannot occur. In addition, the preheat function
will not be possible when the breaker has opened.

Schematic

_

Pictorial

r

1 1

'■ «TAHTiMa

CB3

)

1

© • (

i 1

m

f

II Ml

15A l|

M *•/»» >o M c •»*»

Figure 2. The 10 Amp Circuit Breaker

14 AMP FUSE:

Should the fuse element melt open due to an over­

load, engine cranking and startup will not be possible.

If the fuse must be replaced, use only an Identical 14

amp replacement fuse.

Schematic

Pictorial

15A ■

i

1

' ....... . I»««

© •

•S 14 AH»

m

Figure 3. The 14 Amp Fuse

CRANK RELAY (CR1):

The crank relay (CR1) is energized by battery voltage

when the starl/stop switch is set to Its "Start" position.
When energized, the relay’s nonmally-open contacts
close to perform the following functions:

DDeliver 12 volts DC to the engine control circuit

board, for board operation while cranking.

□connect Terminal 3 of the engine control circuit

board and Wire 17A to ground. The circuit board

then responds by energizing a starter contactor to

initiate engine cranking.

□Deliver 12 volts DC to the engine preheat circuit.

PAGE 5.2-2

Advertising