SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)

1

PARTI

THE REVOLVING FIELD AC GENERATOR

Components In Generator Control Panel (Continued)

FIELD BOOST CIRCUIT

During engine cranking, an engine controi circuit

board deiivers battery voltage to the Rotor w indings.

This "Field Boost" current is delivered to the Rotor via
W ire 4A, a field boost resistor, and W ire 4. The Field

Boost feature provides the follow ing benefits:

□ In effect, field boost current "flashes the field" on

every engine startup. Thus, if Rotor residual m agne­
tism w as lost for any reason, it w ould be restored by

the act of "flashing the field" during cranking.

□ Approxim ately 4-8 volts AC output from the stator

excitation w inding is needed to turn the voltage reg­
ulator on. Reid boost current builds Rotor m agnetism

early w hich, in turn, develops voltage early during
startup. The result of field boost is an early "pickup"
voltage in the stator w indings.

THERMAL PROTECTOR:

Refer to "

TH ERM AL PROT ECTO R'

on Page 1.3-7.

PAGE 1.4-6