SECTION 5.8

TROUBLESHOOTING FLOW CHARTS

1

PARTS

ENGINE ELECTRICAL SYSTEM

Problem IB- Engine Will Not Crank (Type 2 DC Control System

T

NO

i

IS 10 AMP
CIRCUIT
BREAKER
(CB3)
CLOSED?

i—• YESa^

TEST 1-CHECK

14 AMP

FUSE

(FI)

FUSE

w

O.K.“^

TEST 2-CHECK

BATTERY

CABLES

TEST 3-CHECK

THE

BATTERY

FUSE IS BAD

CLOSE

CIRCUIT

BREAKER

i,

BAD

I

REPLACE FUSE

CLEAN, TIGHTEN OR

REPLACE AS NEEDED

BAD

i

RECHARGE

OR REPLACE

IF BATTERY IS GOOD

TEST 12-CHECK

TEST 6-CHECK

DC VOLTS AT

«O.K.^

VOLTAGE AT

TERMINAL 1 OF

TERMINAL 7 OF

ENGINE CONTROL

ENGINE CONTROL

CIRCUIT BOARD

CIRCUIT BOARD

BAD

I

BAD

I

■ O.K.

TEST 7-TEST

TEST 11-TEST

STARTER

STARTER

CONTACTOR

OPERATION

TEST 9-TEST

10 AMP
CIRCUIT
BREAKER
(CBS)

TEST 8-TEST

START/STOP

SWITCH

BAD

I

BAD

\

REPLACE
STARTER

CONTACTOR

REPAIR

OR

REPLACE
STARTER

BAD

1

GOOD

REPLACE BAD

CIRCUIT BREAKER

BAD

i

REPLACE

SWITCH

GOODi

1^ REPLACE ENGINE CONTROL

CIRCUIT BOARD

TEST 13-CHECK

WIRING BETWEEN

BATTERY AND

ENGINE CONTROL

CIRCUIT BOARD

^

REPAIR, RECONNECT

^ OR REPLACE

BAD WIRE(S)

PAGE 5.8-2