SECTION 5.5
ENGINE PROTECTIVE DEVICES

1

g. As the fluid tem perature drops below about 245‘-
266' F., the sw itch contacts should open and the
m eter should indicate 'infinity*.

test.

Replace the high tem perature sw itch if it faiis the

HIGH COOLWr

TEMFeVJVRE «•

SHLTT DOWN'

SWITCH TESTING

TW W 40W ETE»'

//7

m i

/

,

Figure 3. Testing Coolant T em perature Sw itch

Overspeed Protection

General; Generator AC frequency signals are de­

livered to Term inals 5 and 6 of the engine control circuit
board, via W ires 11 and 22. Should engine-generator
speed exceed approxim ately 69-71 Hertz (2070-2130
rpm ), and should such an overspeed last longer than
about four (4) seconds, circuit board action w ill cause

an engine shutdow n.

Testing Overspeed Shutdow n: To test over­

speed shutdow n operation proceed as follow s:

1. Connect an accurate AC frequency m eter to Term i­
nals 5 and 6 of the engine control circuit board (W ires

11 and 22).

2. Start the engine, let it stabilize and w arm up. DO NOT

CONNECT ANY ELECTRICAL LOADS DURING THE

TEST.
3. Slow ly increase engine speed until the frequency

m eter reads about 69 Hertz. Then, slow ly increase
speed to just slightly m ore than 71 Hertz. After a four
(4) second delay, the engine should shut dow n.

Adjusting Overspeed Shutdow n: To adjust the

overspeed setting at w hich engine shutdow n occurs,
proceed as follow s:

1. See Figure 4. Turn the OVERSPEED SHUTDOW N
POTENTIOMETER all the w ay clockw ise against its

stop. DO NOT FORCE.
2. Start the engine, let it stabilize and w arm up at

no-load.
3. Connect an AC frequency m eter across circuit board

term inals 5 and 6 (W ires 11 and 22).

PART 5

ENGINE ELECTRICAL SYSTEM

4. SLOW LY increase engine speed until the frequency

m eter reads about 70 Hertz. Hold that setting, then
SLOW LY

turn

the

OVERSPEED

SHUTDOW N

PO­

TENTIOM ETER

counterclockw ise

(CCW )

IN

VERY

SMALL INCREMENTS. W ait about four (4) seconds
betw een each increm ental adjustm ent. W hen engine
shuts dow n, overspeed shutdow n setting is correct.

Figure 4. Engine Control Circuit Board

PAGE 5.5-2