Part 1 the revolving field ac generator – Generac Power Systems 53187 User Manual

Page 46

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SECTION 1.7- TROUBLESHOOTING
(UNITS WITH 10 INCH STATOR)

1

PART 1

THE REVOLVING FIELD AC GENERATOR

Diagnostic Tests (Continued)

TEST 12- CHECK W IRES 1 AND 4;

Discussion: An open or shorted condition in W ires

1 and 4 w ill have the sam e result as an open or shorted
Rotor w inding.

Procedure: Carefully inspect W ires No. 1 and 4,

betw een the Voltage Regulator and the Brushes. Look
for im proper connections, dam aged insulation, condi­
tion of w ire term inal ends, etc. Use a VOM to check the

w ires for an open or shorted condition.

Results:

1. Reconnect, repair or replace defective w ire(s) as

necessary.

2. If w ires are good, go to Test 13.

TEST 13- TEST STATOR AC POW ER W INDINGS:

Discussion: During the fixed excitation test, the

generator’s AC output voltage should have been ap­
proxim ately one-half rated voltage. It voltage w as less

than one-half rated voltage, one possible cause m ight

be an open, shorted or grounded stator AC pow er

w inding. You m ay w ish to review 'STATOR AC CON­

NECTION SYSTEM '

on Page 1.5-2.

Procedure: To test the stator’s AC pow er w inding,

proceed as follow s:

1. Disconnect and isolate stator leads 11, 22, 33 and

44. See appropriate w iring diagram .
2. Set an accurate VOM to its "Rxl" scale and zero the

m eter.
3. Check for an open circuit condition or for "turn-to-

turn" shorts as follow s:

a. Connect the VOM test probes across stator leads

11 and 22. The resistance of the stator w inding

should be indicated, about 0.21 ohm .
b. Connect the VOM test probes across stator leads

33 and 44. Reading should be approxim ately 0.21
ohm .
c. A reading of "infinity" indicates an open circuit. A

very high reading, indicates a nearly open circuit. A
very low reading indicates "turn-to-turn" shorts.

4. Check for a short betw een parallel w indings as
follow s:

a. Set the VOM to a high resistance scale, such as
"Rxl 0,000" or "RxlK". Zero the m eter.
b. Connect one VOM test probe to stator lead 11, the

other to stator lead 33. The m eter should read "infin-
ity".

5. Check for a grounded condition as follow s:

a. Set the VOM to a high resistance scale, such as
"Rxl0,000" or "RxlK". zero the m eter.
b. Connect one VOM test probe to stator lead 11, the

other to a clean fram e ground on the stator. The VOM
should read "infinity".
c. Now , connect one VOM test probe to stator lead

33, the other to a clean fram e ground on the stator.
The m eter should read "infinity".

Results: Replace the stator if it is open, shorted or

grounded.

TEST 14- CHECK AC VOLTAGE & FREQUENCY:

Discussion:You m ay w ish to review 'ROTOR RO­

TATIONAL SPEECr,

as w ell as 'VOLTAGEAND FRE-

QUENCV

on Page 1.5-2.

Procedure: Refer to Test 1, "CHECK AC OUTPUT

VOLTAGE". Use an accurate AC frequency m eter to
check AC output frequency, as w ell. No-load voltage
and frequency readings should be as follow s:

LIne-to-Neutral Voltage = 121-127 volts AC

LIne-to-llne Voltage = 242-254 volts AC

AC Output Frequency = 60.5-63.5 Hertz

Results:

1. If voltage and frequency are both correspondingly

low or high, go to Test 15.
2. If frequency is good, but voltage is LOW , go to Test
3.
3. If frequency is good, but voltage Is HIGH, go to Test
9.

TEST 15- ADJUST ENGINE GOVERNOR:

Discussion: See "Discussion" under Test 14,

above.

Procedure: Check and adjust the engine governor

as outlined in Section 1.9, “OPERATIONAL TESTS
AND ADJUSTM ENTS'.

Results:

1. If voltage and frequency are now acceptable, stop

tests.
2. If frequency is now acceptable, but voltage is low , go

to Test 3.

TEST 16- CHECK W IRES 2, 2A, AND 6:

Discussion: Unregulated AC output voltage from

the stator excitation w indings is deiivered to the voltage

regulator via W ires 2, 2A and 6. An open condition in
any part of this circuit w ill prevent excitation current
from reaching the reguiator and the Rotor.

Procedure: Refer to appropriate w iring diagram .

Carefully inspect the w ires for dam age, incorrect con­
nections, burned insulation, etc. Use a VOM to test

each w ire for an open or shorted condition.

Results: Reconnect, repair or replace any dam ­

aged or defective w ire(s).

TEST 17- CHECK FOR OVERLOAD CONDITION:

Discussion: The generator should never be over­

loaded. That is, the total of all electrical loads con­
nected at one tim e should not be greater than the unit’s

rated w attage/am perage capacity. If the generator is
overloaded, rpm , frequency and voltage can drop
sharply. In addition, the stator w indings can heat up and
cause the therm al protector to trip (open). If frequency
and voltage drop excessively w hen electrical loads are
applied, m ake sure the unit is not overloaded.

PAGE 1.7-8

Advertising