Part 1 the revolving field ac generator – Generac Power Systems 53187 User Manual

Page 34

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SECTION 1.6- TROUBLESHOOTING
(UNITS WITH 15 INCH STATOR)

1

PART 1

THE REVOLVING FIELD AC GENERATOR

Detailed Instructions (Continued)

1. Set a VOM to Its ’Rxl ’ scale eind zero the m eter.

2. Connect the VOM test probes across W ire No. 5 and

Pin 6 of the Voltage Regulator. The m eter should read

the resistance of the stator excitation w inding (about

0. 53.ohm ).
3. Now , set the VOM to a very high resistance scale

such as ’Rx10,000" or "Rx1 K". Again, zero the m eter.

a. Connect one VOM test lead to bypass W ire No. 5,

the other to a clean fram e ground on the stator. The
m eter should Indicate "infinity".

b. Any reading other than "infinity" indicates a shorted
condition and the stator should be replaced.

4. W ith the VOM still set to a high resistance scale,
connect one VOM test probe to stator W ire No. 5, the

other to stator ac output W ire No. 11 or 22. "Infinity"
should be Indicated.

5. Connect the VOM test probes across W ire No. 5 and
stator AC output W ire No. 33. "Infinity" should be indi­
cated.

Results:

1. If the stator excitation w inding fails any part of the test,

replace the stator assem bly.
2. If the stator excitation w inding checks good, go on to

Test 6.

Figure 4. Excitation W inding Test Points

TEST 6- TEST THERM AL PROTECTOR:

Discussion: You m ay w ish to review the inform ation

on the therm al protector. See Page 1.3-7.

Procedure: Set a VOM to its "Rxl" scale and zero

the m eter. Connect the VOM test probes across stator
w ires No. 2 and 6. See Table 1, Page 6.1-1 for nom inal

resistances.

Results:

1. If norm al excitation w inding resistance w as indi­

cated in Test 5, but "infinity" w as Indicated in Test 6, the
thërm al protector is open and m ust be bypassed.

2. If norm al excitation w inding resistance w as indi­

cated in both Tests 5 and 6, the therm al protector is

good. Go on to Test 7.

TEST 7- TEST EXCITATION LEADS:

Discussion: An open or shorted condition in the

stator excitation w inding's output leads to the Regulator

w ill cause com plete or partial loss of the unregulated
excitation current to the Regulator.

Procedure: Inspect W ires No. 2,6 and 162, betw een

the stator and the Voltage Regulator. Make sure they

are properly connected and undam aged. Use a VOM to

test the w ires tor "continuity".

Results:

1. Reconnect, repair or replace any dam aged, discon­

nected or shorted w ire(s).

/

2. If all excitation leads are good, go to Test 11.

TEST 8- CHECK REGULATOR SENSING LEADS:

Discussion: An open or shorted condition in the

sensing leads to the Voltage Regulator w ill result in loss
of sensing (actual voltage) signals to the Voltage Reg­
ulator. The Regulator’s "Sensing" lam p w ill then go out.

Procedure: Carefully inspect W ires SI 5 and SI6,

betw een the Regulator and the sensing transform er.

Also inspect W ires No. 11 and 22, betw een the sensing
transform er and the stator. Use a VOM to test all w ires
for an open or shorted condition.

Results:

1. Reconnect, repair or replace any disconnected,

dam aged or defective w ire(s).

2. If the sensing leads are good, go on to Test 9.

TEST 9- TEST SENSING TRANSFORMER:

Discussion: The Part No. 67680 Voltage Regulator

requires a 240 volts AC sensing signal to operate
properly. You m ay w ish to review the inform ation on the
sensing transfonm er on Page 1.3-6.

PAGE 1.6-6

Advertising