PARTI

THE REVOLVING FIELD AC GENERATOR

1

SECTION 1.4- MAJOR COMPONENTS

Components in Generator Control Panel (Continued)

THE AC VOLTAGE REGULATOR:

The VoKage Regulator used on units w ith 10 inch

stator is show n In Figure 10. The Regulator has a single
red lam p (LED) w hich w ill rem ain on during operation

as long as stator AC pow er w inding "sensing* voitage is
avaiiabie. Three sets of leads connect to the Regulator

term inals as follow s:

D

Unregulated AC output from the stator excitation

w inding connect to the tw o term inals indicated by

"DPE*.

Sensing (actual) voltage signals from the stator

AC pow er w indings are delivered to the

Regulator term inals indicated by "SEN".

Rectified and regulated (DC) current Is delivered

to the Rotor w inding from Regulator term inals

Indicated by a"+" and

The Regulator provides over-voltage protection. On

loss of "sensing", the Regulator w ill shut dow n and

regulated excitation current to the Rotor w ill term inate.

A single adjustm ent potentiom eter perm its the gener­

ator's AC output voltage to be adjusted. Perform this

adjustm ent w ith the engine running at no-load and w ith

AC frequency at 62 Hertz (1860 rpm ). At 62 Hertz, set

the line-to-neutral AC output voltage to 124 volts AC; or
the line-to-line AC output voltage to 248 volts AC.

AC CIRCUIT BREAKERS:

Tw o AC output circuit breakers (CB1 and CB2) are

provided, one for each line of the 240 volts AC output
circuit. The trip rating of these breakers depends on the
rated m axim um am perage capacity of the generator.
Units rated at 8000 w atts (8.0 kW ) are equipped w ith AC

breakers rated at 35 am peres.

Schem atic

Pictorial

1

1

SEE FIGURES 4 & 5 ON

PAGE 1.5-2 FOR W IRING
CONNECTIONS

Figure 11. AC Output Circuit Breakers

EXCITATION CIRCUIT BREAKER (CB4):

An AC circuit breaker, rated 5 am peres, is electrically

connected in series w ith W ires No. 2 and 2A betw en the

stator excitation w inding and the Voltage Regulator. If

the breaker should trip (open) due to an overload, loss

of excitation current to the Rotor w ill occur. Generator

AC output voltage w ill then decrease to a value that is

com m ensurate w ith Rotor residual m agnetism (about 2

to 7% of the unit's rated voltage). The breaker is self

resetting and cannot be reset m anually.

Figure 12. Excitation Circuit Breaker

PAGE

1.4-5