NuDAM-6521

51

5.2 Initialation & Installation

Software Installation

1. If you have already installed “NuDAM Administration” then skip other steps.

2. Backup your software diskette

3. Insert “NuDAM Administration” disc into CD-ROM:

4. Change drive to the path of CD-ROM. For example, your drive of CD-ROM is

F:, then change the drive to F:

5. Find the setup of NuDAM Administration and run it.

6. Please follow the steps of setup program then you can successful to install the

nudism Administration.

Objective of Initializing a Brand-New NuDAM-6521

All NuDAM modules. except NuDAM-6520, 6510, and 6530, in a RS-485
network must have an unique address ID, however, every brand-new
NuDAM-6521 has a factory default setting as following:

Address ID is 01.

Baud rate is 9600 bps

RS-485 Interface

Host Watchdog timer is disable

Therefore, to configure the brand-new NuDAM before using is necessary,
otherwise the address ID will be conflict with others modules because the ID of
new modules are identity . The baud rate may also be changed according to
user‘s requirements.

Default State

The NuDAM I/O modules must be set at Default State when you want to change
the default settings, such as the ID address, baud rate, check-sum status etc.
All NuDAM I/O modules have an special pin labeled as DEFAULT*. The module
will be in Default State if the DEFAULT* pin is shorted to ground when power
ON. Under this state, the default configuration is set as following:

Address ID is 00.

Baud rate is 9600 bps.

RS-485 Interface