ADLINK ND-6520 User Manual

Page 64

Advertising
background image

60

NuDAM-6521

5.4.4 Read Configuration

@Description
Read the configuration of module on a specified address ID.

@Syntax
$(Addr)2<CR>

$

Command leading code

(Addr) Address

ID.

2

Command code for reading configuration

@Response
!(Addr)(TypeCode)(BaudRate)(DataFlag)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(TypeCode)

It always be 40 (Hex)

(BaudRate)

Current setting of communication baud rate of
RS-422/485 and RS-232, refer to Table 3-1 for
details.

(DataFlag) Current

setting

of module setting and RS-232

configuration. Refer 3.3 for details.

@Example

User command:

$302<CR>

Response:

!3040662103<CR>

!

Command is valid.

30 Address

ID.

40

Digital I/O module.

66

Baud rate is 9600 for RS-422/485 and RS-232.

2103 Addressable

mode

Checksum is disable
RS-485 interface
Append <CR>
Non-parity
8 data bit

5.4.5 Read Module Name