52

NuDAM-6521

Therefore, the communication between host and the module will can be easily
set as the same configuration, the initialization of a module will be possible no
matter what configuration is set under operating state

Initialization Equipments

Host computer with an RS-232 port.

An installed RS-485 module (NuDAM-6520 or 6530) with 9600 baud
rate.

The brand new NuDAM-6521

Power supply (+10 to +30 V

DC

) for NuDAM modules

Administration utility software

Note1: Never Connect the DRFAULT* pin to Vs or power source

just left it open or wired to GND.

Initialization Procedure

1. Power off the host computer and the installed NuDAM-6520 or 6530. Be sure

of the baud rate of the NuDAM-6520 or 6530 is 9600 bps.

2. Connect a brand new NuDAM module with the RS-485. Set the module in

Default State by shorting the DEFAULT* pin. Refer to Figure 5.1 for detailed
wiring.

3. Power on the host computer.

4. Power on the power supply for NuDAM modules.

5. Use the NuDAM Administrating utility to configure the address ID, Baud rate

and check-sum status of the module.