Softkeys – LINK Systems OmniLink II Press Automation Control User Manual

Page 44

Advertising
background image

August 30, 2002 Manual Version 1.0

3.11

Section 3.9.3 Code (Password) System Operation

If any of the access modes to Program Mode that use a code is chosen in the User Configuration Mode,
code access to the system to perform setting(s) or action(s) is a log on operation that requires a user to
enter his name (or classification) and a code associated with the user name. The system will also ask for
a name and code whenever softkeys that allow access to settings or actions restricted to Program Mode,
such as reset or bypass, are pressed. Once the user has logged on with his user code through any
screen, access to other settings and actions permitted by his code in other screens is available until
manual or automatic log out.


The following example of code access to Program Mode shows the steps necessary to access settings by
code for new entry or change through the Die Protection screen if the User Configuration is set to allow
code access. It should be noted that log on may also be required to reset or bypass the die protection
function in the example shown when a reset or bypass softkey is pressed. Although screens for
programmable limit switch and other functions are somewhat different, a common feature will be that
the code request sequence to settings will always be by means of the upper right softkey, whereas the
code request sequence for actions is initiated by the softkey that performs the action. Further, a user
with proper access code can always log on by pressing the SUPPLY ACCESS CODE softkey that
appears at the top of the Brake Monitor and Diagnostic screen in Run Mode. The popup Select User
Name table and user name Code Entry box that are shown later in this example will also appear on all
other screens where access to settings or actions by code (password) is used.























Figure 3.9 Main Die Protection Screen for Module 1, Channels 1-8


Figure 3.9 shows the main Die Protection screen as it appears with one of the code access options to
access Program Mode configured. To change settings for Die Protection with a code, select the screen
with the module and channel number(s) for which you wish to enter or change settings. The NEXT
PAGE and PREVIOUS PAGE softkeys are used to select a module (in many cases there will only be 1

In Code Access Mode,
the Channel Settings Softkey
will select the DP Channel
Settings screen so settings
can be viewed in Run Mode,
but the SUPPLY ACCESS
CODE softkey must be
pressed and user name and
code entered to change
settings on the DP Channel
Settings screen.

Stroke

Mode

Drive

Speed
Stroke
Speed

SPM

SPM

0

0

Order

Counter

SYSTEM STATUS

Counter OFF

Die

Protection

CHANNEL

SETTINGS

CHANNE L

DIAGS

NEXT

PAGE

0

0

OK

TO P

EXIT

Ch Channel T ype

Description

Status

State

1 Stat ic

Stock Buckle

OK

Of f

2 Not Used

OK

Of f

3 1 Part Dete ctor Edge

Par t Out

OK

Of f

4 In Position

Die Cam Retract ed

OK

On

5 Cyclic

Str ipper Le ft Front

OK

Of f

6 Cyclic

Str ipper Right Front

OK

Of f

7 Cyclic

Str ipper Le ft Rear

OK

Of f

8 Cyclic

Str ipper Right Rear

OK

Of f

Module 1 - Channe l 5 Det ails

Input Type:

Stop Type:

Bypassed:

Delay Time:

Delay St rokes:

Window On:

Window Of f:

Normally O FF
Top Stop
No
0 msecs
0 Strokes
154

0

213

0

0

90

270

180

Channel

Status

OK

System Status: OK

Module Status: OK

SoftKeys

5

RESET
FAULT

Appears in both Program and
Run when a Die Protection
fault occurs.

Advertising