Blower performance data, Ab e, Nlv080 - blower performance data – WaterFurnace Envision (XL) User Manual

Page 15

Advertising
background image

ENVISION 7-25 TONS INSTALLATION MANUAL

16

Airflow in CFM with dry coil and clean air filter.

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

BHP

0.29

0.33

0.38

0.37

0.45

0.47

0.50

0.54

0.58

0.64

0.69

0.71

0.73

0.84

0.95

1.05

RPM

437

478

518

539

586

617

647

677

707

736

765

775

809

843

876

909

TURNS OPEN

4.0

3.0

2.0

1.5

5.0

4.5

4.0

3.5

3.0

2.5

2.0

3.5

3.0

2.5

2.0

1.5

MTR/SHEAVE

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

5.0

BHP

0.38

0.44

0.43

0.52

0.56

0.59

0.63

0.68

0.73

0.78

0.81

0.83

0.94

1.05

1.13

1.20

RPM

477

517

538

585

615

645

675

704

734

763

774

807

841

874

907

940

TURNS OPEN

3.0

2.0

1.5

5.0

4.5

4.0

3.5

3.0

2.5

2.0

3.5

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

5.0

BHP

0.49

0.50

0.59

0.63

0.67

0.72

0.77

0.83

0.89

0.91

0.94

1.05

1.17

1.24

1.32

RPM

516

537

584

614

643

673

702

732

761

772

806

839

871

905

938

TURNS OPEN

2.0

1.5

5.0

4.5

4.0

3.5

3.0

2.5

2.0

3.5

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

5.0

BHP

0.56

0.66

0.71

0.75

0.81

0.86

0.92

0.99

1.02

1.05

1.17

1.29

1.37

1.44

RPM

536

582

612

642

671

700

729

758

770

804

837

869

903

936

TURNS OPEN

1.5

5.0

4.5

4.0

3.5

3.0

2.5

2.0

3.5

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

5.0

BHP

0.72

0.78

0.83

0.89

0.95

1.02

1.09

1.12

1.16

1.29

1.41

1.49

1.57

RPM

581

611

640

669

698

727

756

768

802

835

867

900

933

TURNS OPEN

5.0

4.5

4.0

3.5

3.0

2.5

2.0

3.5

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

5.0

BHP

0.83

0.90

0.97

1.03

1.11

1.18

1.14

1.27

1.40

1.53

1.61

1.70

RPM

610

639

668

697

726

754

767

800

833

865

898

930

TURNS OPEN

4.5

4.0

3.5

3.0

2.5

2.0

3.5

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

BHP

0.97

1.04

1.11

1.19

1.23

1.30

1.37

1.51

1.64

1.73

1.82

RPM

637

666

695

725

731

765

798

830

862

895

927

TURNS OPEN

4.0

3.5

3.0

2.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

Bold Face Requires 1.5 HP Motor

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr

Units factory shipped with standard static sheave and drive at 3 turns open (2600 cfm @ 0.6 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 3 turns open (2600 cfm @ 0.6 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12in. wg.

2800

3000

3200

3400

Rated CFM

2200

2400

2600

A

B

E

07/25/07

NLV080 - Blower Performance Data

Belt Drive

Advertising